{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV846211","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV846211","canonicalUrl":"https://aoctrl.com/schneider/LV846211","factsUrl":"https://aoctrl.com/api/mcp/products/LV846211","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPact MTZ2, LV846211, 4P drawout circuit breaker, 1000 A at 40 °C, H2V 100 kA 415 V AC, Category B.","salesMarkdown":"The LV846211 is a 4-pole MasterPact MTZ2 drawout circuit breaker rated 1000 A at 40 °C, with an H2V performance class delivering 100 kA Ics at 440 V AC. That Ics figure — 100 kA at both 220/415 V and 440 V — means it clears a bolted fault at full rated voltage without losing the ability to carry rated current afterward, which is the difference between a one-time fuse and a reusable breaker in a main or tie position. The 12 kV Uimp impulse withstand and 100 kA Icw for 1 second confirm it holds through delayed trips on downstream faults, essential for selective coordination in a Category B installation. Drawout mounting means the breaker chassis stays wired to the bus; the removable cradle pulls for maintenance or swap without disturbing power connections. Suitability for isolation per EN/IEC 60947-2 is confirmed, meaning the open breaker provides a visible disconnect gap for safe maintenance access. ## Deployment context Intended for power distribution protection in main switchboards, distribution panels, and generator or UPS tie points. The drawout form factor suits installations where uptime matters — a spare cradle can be pre-wired and swapped in during a fault event without de-energizing the bus. Ambient operating range of -25 to 70 °C covers most conditioned electrical rooms; storage down to -40 °C is fine for unheated warehouses.","metaTitle":"LV846211 MasterPact MTZ2 4P Drawout Breaker, 1000 A, 100 kA","metaDescription":"Schneider Electric LV846211 MasterPact MTZ2 4P drawout circuit breaker, 1000 A rated current, 100 kA Ics at 440 V AC, H2V performance. Current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"403 mm","Width":"556 mm","Height":"439 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP30","Application":"Power distribution protection","Control Type":"Push-button","Product Status":"Active","Terminal Pitch":"115 mm","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"1000 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front Rear","Electrical Life Cycles":"10000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-2 AC-23 A: 10000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3","Mechanical Life Cycles":"15000 cycles with periodic preventive maintenance","Connection Surface Bottom":"Front Rear","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$4,882.68","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/69ce3bb6505a1049aaef3a6111c234d3.pdf","sourceUrl":"https://www.se.com/ph/en/product/LV846211/circuit-breaker-masterpact-mtz2-10-h2v-1000-a-4-poles-drawout-without-trip-unit-right-neutral/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV846211/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV846211","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV846211 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}