{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV846212","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV846212","canonicalUrl":"https://aoctrl.com/schneider/LV846212","factsUrl":"https://aoctrl.com/api/mcp/products/LV846212","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPacT, MasterPact MTZ2, circuit breaker, LV846212, 4P, 1250 A at 40 °C, H2V 100 kA at 415 V AC, drawout mounting.","salesMarkdown":"The LV846212 is a MasterPact MTZ2 4-pole drawout circuit breaker rated 1250 A at 40 °C. For selectivity coordination, Category B means it has intentional short-time delay, so downstream breakers trip first; the 100 kA Icw for 1 second gives the time margin to achieve full discrimination in a distribution panel. ## Deployment context Drawout mounting means the breaker chassis stays wired in the switchgear while the moving portion racks out for maintenance or replacement — standard for main and tie breakers in 400 V to 690 V industrial distribution where uptime matters. The 403 mm depth and 556 mm width fit standard low-voltage switchgear cubicles; connection pitch is 115 mm. Front and rear connection options allow either cable or busbar entry without reconfiguring the cradle. Rated for isolation — the open contacts provide a visible gap that meets the safety disconnection requirement. IP30 enclosure protection keeps tools and fingers out but is not washdown-rated; the breaker lives inside a switchgear cubicle, not on the open floor. ## Electrical durability and thermal budget Electrical durability: 10,000 cycles at 440 V AC, 50/60 Hz at In per EN/IEC 60947-2 AC-23A, and 6,000 cycles per AC-3. Mechanical durability is 15,000 cycles with periodic preventive maintenance. Maximum breaking time is 25 ms; closing response is 70 ms. Power dissipation at rated current is 230 W — factor that into the cubicle ventilation calculation.","metaTitle":"LV846212 MasterPact MTZ2 4P Drawout, 1250 A, 100 kA","metaDescription":"LV846212 MasterPact MTZ2 4P drawout circuit breaker, 1250 A at 40 °C, 100 kA breaking capacity at 440 V. Active production. Sourced to order. Complies with EN/IEC 60947-2.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"403 mm","Width":"556 mm","Height":"439 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP30","Application":"Power distribution protection","Control Type":"Push-button","Product Status":"Active","Terminal Pitch":"115 mm","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"1000 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front Rear","Electrical Life Cycles":"10000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-2 AC-23 A: 10000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3","Mechanical Life Cycles":"15000 cycles with periodic preventive maintenance","Connection Surface Bottom":"Front Rear","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$5,319.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ddbeff2014f8ef44f27e63599718ad51.pdf","sourceUrl":"https://www.se.com/vn/en/product/LV846212/circuit-breaker-frame-masterpact-mtz2-12h2v-drawout-for-micrologic-x-1250a-100ka-415vac-icu-icw-4p-right-neutral/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV846212/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV846212","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV846212 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}