{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV846213","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV846213","canonicalUrl":"https://aoctrl.com/schneider/LV846213","factsUrl":"https://aoctrl.com/api/mcp/products/LV846213","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPacT series, MasterPact MTZ2 drawout circuit breaker, LV846213, 4P, 1600 A at 40 °C, H2V 100 kA 415 V AC performance type.","salesMarkdown":"## MasterPact MTZ2 1600 A — selectivity and breaking capacity for main distribution The Schneider Electric LV846213 is a MasterPact MTZ2 drawout circuit breaker rated 1600 A at 40 °C, 4 poles, with a H2V performance type delivering 100 kA breaking capacity at 415 V AC. This places it in the Category B selectivity class per EN/IEC 60947-2, meaning it's designed for main incoming or large feeder duty where full discrimination with downstream breakers is required — a line-down event on a fault clears the branch, not the main. The making capacity (Icm) at 440 V AC is 220 kA, which is the peak let-through the breaker must close onto and hold under fault. ## Drawout mounting and connection flexibility Drawout mounting means the breaker chassis stays wired to the bus while the moving portion can be racked out for maintenance or swap — no need to disconnect power cables. Both upside and downside connections accept front or rear termination, which simplifies bus-bar routing in switchgear lineups. The connection pitch is 115 mm, and the mounting support accommodates rails or a base plate. Physical envelope: 556 mm wide × 439 mm high × 403 mm deep. Neutral is on the right. ## Durability and environmental ratings Electrical durability is 10,000 cycles at rated current at 440 V AC per EN/IEC 60947-2 (AC-23A), and 6,000 cycles per EN/IEC 60947-3 (AC-3). Mechanical durability is 15,000 cycles with periodic preventive maintenance. IP30 protection is typical for enclosed switchgear — the enclosure provides the higher IP rating. Operating altitude is 0 to 2000 m without derating, 2000 to 5000 m with derating.","metaTitle":"Schneider Electric LV846213 MasterPact MTZ2 1600A 4P Circuit","metaDescription":"Schneider Electric LV846213 MasterPact MTZ2 drawout circuit breaker, 1600A at 40°C, 4P, H2V 100kA at 415V AC. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"403 mm","Width":"556 mm","Height":"439 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP30","Application":"Power distribution protection","Control Type":"Push-button","Product Status":"Active","Terminal Pitch":"115 mm","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"1000 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front Rear","Connection Surface Bottom":"Front Rear","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$6,954.66","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7bc901345fbc78f8df14048db9ef996b.pdf","sourceUrl":"https://www.se.com/au/en/product/LV846213/circuit-breaker-frame-masterpact-mtz2-16h2v-drawout-for-micrologic-x-1600a-100ka-415vac-icu-icw-4p-right-neutral/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV846213/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV846213","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV846213 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}