{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV846217","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV846217","canonicalUrl":"https://aoctrl.com/schneider/LV846217","factsUrl":"https://aoctrl.com/api/mcp/products/LV846217","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPact MTZ2 drawout circuit breaker, LV846217, 4P, 4000 A at 40 °C, H2V 100 kA 415 V AC, Category B, IP30.","salesMarkdown":"## MasterPact MTZ2 4000 A drawout — selectivity and arc energy management The Schneider LV846217 is a MasterPact MTZ2 drawout circuit breaker rated 4000 A at 40 °C with a H2V performance class delivering 100 kA breaking capacity at 415 V AC. That 100 kA Icu at 440 V AC and 100 kA Icw for 1 second give it the short-time withstand to coordinate downstream breakers in a Category B selective scheme — meaning a fault on a feeder branch clears without dropping the main bus. The 220 kA Icm making capacity handles the first asymmetric peak of a bolted fault without contact welding. The 115 mm connection pitch matches standard MasterPact busbar stacks and rear-connection adapters. Neutral is on the right. The control type is push-button with no separate control unit — the breaker ships as a bare frame, so you'll add the Micrologic trip unit separately based on your protection curve needs (LSIG, LSIV, etc.). Power dissipation runs 900 W at rated current — factor that into enclosure ventilation. The IP30 degree of protection is standard for switchgear compartments; it keeps accidental finger contact out but isn't washdown-rated. Altitude derating kicks in above 2000 m. ## Mechanical and electrical endurance Mechanical durability is 15,000 cycles with periodic preventive maintenance. Electrical endurance at rated current: 5,000 cycles at 440 V AC under AC-23A (switching motor loads or mixed loads), and 6,000 cycles under AC-3 (motor switching) per EN/IEC 60947-3. Maximum breaking time is 25 ms, closing response time 70 ms. These numbers define the preventive maintenance interval — plan an inspection at around 12,000 mechanical operations or 4,000 electrical operations under load. ## Physical integration Dimensions: 556 mm wide, 439 mm high, 403 mm deep. Mounting support is rails or base plate. The drawout cradle means the breaker slides into a fixed chassis — you wire the cradle once, then the breaker inserts or withdraws for maintenance without disturbing the power connections. Plan for the 115 mm pole pitch when laying out busbar drops or rear-connection adapters.","metaTitle":"Schneider LV846217 MasterPact MTZ2 4000A, 100kA 415V AC","metaDescription":"Schneider LV846217 MasterPact MTZ2 drawout circuit breaker, 4000 A rated, 100 kA breaking at 415 V AC. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"403 mm","Range":"MasterPacT","Width":"556 mm","title":"LV846217","Height":"439 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12","description":"circuit breaker, Masterpact MTZ2 40 H2V, 4000 A, 4 poles, drawout, without trip unit, right neutral","Control type":"Push-button","Control unit":"Without control unit","Product name":"MasterPact MTZ2","Mounting mode":"Drawout","Sensor rating":"2000 A 2500 A 3200 A 4000 A","lifecycle_stage":"current","Connection pitch":"115 mm","Mounting support":"Rails Base plate","Neutral position":"Right","Performance type":"H2V 100 kA 415 V AC","Pollution degree":"3 conforming to IEC 60947-1","Device short name":"MTZ2 40 H2V","Poles description":"4P","Upside connection":"Front Rear","Device application":"Power distribution protection","Operating altitude":"0...2000 m without derating 2000...5000 m with derating","[In] rated current":"4000 A at 40 °C","Downside connection":"Front Rear","Selectivity category":"Category B","Electrical durability":"5000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-2 AC-23A: 5000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3","Maximum breaking time":"25 ms","Mechanical durability":"15000 cycles with periodic preventive maintenance","Power dissipation in W":"900 W","IP degree of protection":"IP30 conforming to EN 60529","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"12 kV","[Icw] rated short-time withstand current":"100 kA 0.5 s 100 kA 1 s 75 kA 3 s","[Icm] rated short-circuit making capacity":"220 kA 220/415 V AC at 50/60 Hz 220 kA 440 V AC at 50/60 Hz","[Icu] rated ultimate short-circuit breaking capacity":"100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$21,209.04","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/dfb1a9413c018dbcf19c71d1f130fd5e.pdf","sourceUrl":"https://www.se.com/ph/en/product/LV846217/circuit-breaker-masterpact-mtz2-40-h2v-4000-a-4-poles-drawout-without-trip-unit-right-neutral/"},"ai":{"faq":[{"question":"Who supplies LV846217 and how is it quoted for volume purchases?","answer":"The LV846217 is sourced through independent distribution channels. Submit an RFQ with your target quantity and delivery window — availability and current pricing are confirmed at quote time."},{"question":"What is the closest alternative to LV846217 in the MasterPact family?","answer":"Within the MasterPact MTZ2 range, the closest alternative would be a different H2V performance variant at a lower amp rating (e.g., 3200 A or 2500 A) if your load doesn't require the full 4000 A. The frame size, drawout cradle, and connection pitch are shared across MTZ2 frames, so a downsized unit retrofits into the same panel cutout with a trip unit change. No pin-compatible drop-in exists at a different rating — the sensor rating is tied to the frame."},{"question":"What compliance documentation does Schneider provide for LV846217?","answer":"The LV846217 is certified to EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H, and IEC 61557-12. It carries a suitability-for-isolation marking per EN/IEC 60947-2. Standard Schneider documentation includes a Declaration of Conformity to the Low Voltage Directive, a test certificate for the type-tested assembly, and the individual breaker's routine test report. RoHS and REACH declarations are available on request from the manufacturer."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV846217","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV846217 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}