{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV846315","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV846315","canonicalUrl":"https://aoctrl.com/schneider/LV846315","factsUrl":"https://aoctrl.com/api/mcp/products/LV846315","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPact MTZ2 32 HH, LV846315, switch-disconnector, 3200 A, 100 kA Icu at 440 V AC, 4P fixed, EN/IEC 60947-3.","salesMarkdown":"The LV846315 is a MasterPact MTZ2 32 HH switch-disconnector rated for 3200 A continuous current at 440 V AC — that's the main feeder disconnect for a large distribution board or a high-current industrial load center. Isolation capability is confirmed per EN/IEC 60947-3, with a visible contact position indicator (though no physical visible break — the indicator is the tell). Fixed-mount, 4-pole, 537 mm wide by 352 mm tall by 300 mm deep — it's a substantial footprint that needs a dedicated compartment in the switchboard. ## Duty cycles and durability Rated for 5000 electrical cycles in AC-23A duty (switching motor loads and mixed inductive/resistive loads) at 440 V, and 15000 mechanical cycles with periodic preventive maintenance. The AC-3 utilisation category also applies, so it handles the inrush of squirrel-cage motors during starting. Short-time withstand is 75 kA for 3 seconds or 100 kA for 1 second — enough to ride through a delayed trip coordination window.","metaTitle":"LV846315 MasterPact MTZ2 32 HH Switch Disconnector, 3200 A,","metaDescription":"LV846315 MasterPact MTZ2 32 HH switch disconnector, 3200 A rated current, 100 kA Icu at 440 V, 4P fixed. Active production, sourced to order. RFQ for pricing and availability.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"300 mm","Range":"MasterPact","Width":"537 mm","title":"LV846315","Height":"352 mm","Standards":"EN/IEC 60947-3","description":"Switch disconnector, MasterPact MTZ2 32HH, 3200A, 220kA/440VAC 50/60Hz (Icm), 4P, fixed","Control type":"Push-button","Network type":"AC","Mounting mode":"Fixed","Visible break":"No","lifecycle_stage":"current","Connection pitch":"115 mm","Pollution degree":"3 conforming to EN/IEC 60947-4-1","Breaking capacity":"100 kA Icu at 220/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2","Network frequency":"50/60 Hz","Performance Level":"HH","Poles description":"4P","Device application":"Distribution","Utilisation category":"AC-23A AC-3","Electrical durability":"AC-23A: 5000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3","Mechanical durability":"15000 cycles with periodic preventive maintenance conforming to EN/IEC 60947-3","IP degree of protection":"IP30","Switch-disconnector name":"MasterPact MTZ2 32 HH","Product or component type":"Switch disconnector","Suitability for isolation":"Yes conforming to EN/IEC 60947-3","Contact position indicator":"Yes","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to EN/IEC 60947-3","[Ie] rated operational current":"3200 A AC 50/60 Hz 440 V","[Ue] rated operational voltage":"440 V AC 50/60 Hz conforming to EN/IEC 60947-3","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"100 kA at 220/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 100 kA at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"12 kV conforming to EN/IEC 60947-3","[Icw] rated short-time withstand current":"75 kA during 3 s conforming to EN/IEC 60947-3 100 kA during 1 s conforming to EN/IEC 60947-3","[Icm] rated short-circuit making capacity":"220 kA peak 220/415 V AC at 50/60 Hz 220 kA peak 440 V AC at 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$12,864.69","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a29a72048878f67d98598062c8b9a461.pdf","sourceUrl":"https://www.se.com/th/en/product/LV846315/switch-disconnector-masterpact-mtz2-32hh-3200a-220ka-440vac-50-60hz-icm-4p-fixed/"},"ai":{"faq":[{"question":"What is LV846315's breaking capacity?","answer":"100 kA Icu at 220/415 V AC and 100 kA Icu at 440 V AC, both per EN/IEC 60947-2. The rated service breaking capacity (Ics) matches at 100 kA, so it can be reclosed after a fault at full rating."},{"question":"Where can I buy LV846315 and what is the lead time?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for your quantity and delivery window."},{"question":"What standards does LV846315 comply with?","answer":"EN/IEC 60947-3 for switch-disconnectors, EN/IEC 60947-2 for the breaking capacity ratings, and pollution degree 3 per EN/IEC 60947-4-1. Isolation suitability is confirmed to the same standard."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV846315","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV846315 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}