{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV846457","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV846457","canonicalUrl":"https://aoctrl.com/schneider/LV846457","factsUrl":"https://aoctrl.com/api/mcp/products/LV846457","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPacT MasterPact MTZ1, LV846457, drawout circuit breaker, 4P, 630 A rated at 40 °C, H3 66 kA 415 V AC, IEC 60947-2.","salesMarkdown":"The Schneider Electric LV846457 is a MasterPact MTZ1 drawout circuit breaker from the MasterPacT range, built for power distribution protection. It carries a 630 A rated current at 40 °C across four poles, with an H3 performance class delivering 66 kA breaking capacity at 415 V AC. That 66 kA rating means it clears high-fault currents on a 415 V industrial feeder without upstream devices needing to trip — a Category B selectivity device that coordinates with downstream breakers to isolate only the faulted branch. Rated operational voltage (Ue) is 690 V AC 50/60 Hz, with insulation voltage (Ui) at 1000 V AC and impulse withstand (Uimp) at 12 kV — this breaker handles standard 400/480 V distribution and steps up to 690 V for mining or marine gear. Short-time withstand (Icw) holds 30 kA for 3 seconds, critical for selective coordination with downstream devices. Making capacity (Icm) hits 145 kA at 440 V AC, so it closes against a bolted fault without welding contacts. ## Deployment context This is a drawout breaker — the chassis stays wired to the bus, the breaker cassette slides in and out for safe swap without disturbing connections. Mounts on rails or a base plate inside a switchgear lineup. Front and rear connection options give flexibility for cable or busbar entry. IP30 protection suits enclosed switchgear; not for open washdown areas.","metaTitle":"Schneider Electric LV846457 MasterPact MTZ1 630A 4P Drawout","metaDescription":"Schneider Electric LV846457 MasterPact MTZ1 drawout circuit breaker. 630 A rated current, 4 poles, H3 66 kA breaking capacity at 415 V AC. IEC 60947-2. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Voltage":"690 V AC 50/60 Hz","IP Rating":"IP30","Application":"Power distribution protection","Control Type":"Push-button","Product Status":"Active","Terminal Pitch":"70 mm","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"1000 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front Rear","Connection Surface Bottom":"Front Rear","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$3,754.14","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/011495879e782c868dfd47bf065bbd70.pdf","sourceUrl":"https://www.se.com/th/en/product/LV846457/circuit-breaker-frame-masterpact-mtz1-06h3-drawout-for-micrologic-x-630a-66ka-415vac-icu-4p/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV846457/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV846457","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV846457 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}