{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV846555","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV846555","canonicalUrl":"https://aoctrl.com/schneider/LV846555","factsUrl":"https://aoctrl.com/api/mcp/products/LV846555","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPacT MTZ2, LV846555, fixed 4P air circuit breaker, 2500 A rated current, 50 kA at 1150 V AC, Category B, IP30.","salesMarkdown":"The LV846555 is a MasterPact MTZ2 fixed air circuit breaker from the MasterPacT range, rated 2500 A at 40 °C and built for power distribution protection in industrial and commercial switchboards. It's a 4-pole unit with rear connections top and bottom, designed for Category B selectivity — meaning it holds through a downstream fault and only opens when the fault is on its own bus. That selectivity is the key for a plant engineer coordinating a multi-level distribution scheme: you size the main breaker so a feeder fault doesn't take the whole line down. Rated making capacity (Icm) hits 105 kA at 1150 V AC, so it closes against a full bolted fault without welding contacts. For a site electrical engineer, the Icw at 3 seconds is the number that decides whether your coordination study passes. ## Physical integration and environmental limits Fixed mounting on rails or base plate, with a 115 mm connection pitch. IP30 protection means it's suited for indoor switchboards where tools or fingers are the main concern, not hose-down. Also listed to IEC 61557-12 for IT system monitoring. Impulse withstand voltage is 12 kV (Uimp), which covers typical surge environments in industrial distribution. ## Durability and maintenance Mechanical durability is 20,000 cycles with periodic preventive maintenance; electrical durability is 500 cycles at 1150 V AC, 50/60 Hz per IEC 60947-2. Maximum breaking time is 25 ms, closing response time 70 ms.","metaTitle":"LV846555 MasterPact MTZ2 2500 A 50 kA 4P Circuit Breaker","metaDescription":"LV846555 MasterPact MTZ2 2500 A 4P circuit breaker, 50 kA at 1150 V AC, Category B, IP30. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"300 mm","Width":"537 mm","Height":"352 mm","Voltage":"1150 V AC 50/60 Hz","IP Rating":"IP30","Application":"Power distribution protection","Control Type":"Push-button","Product Status":"Active","Terminal Pitch":"115 mm","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"1250 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Rear","Electrical Life Cycles":"500 cycles 1150 V AC 50/60 Hz conforming to EN/IEC 60947-2","Mechanical Life Cycles":"20000 cycles with periodic preventive maintenance","Connection Surface Bottom":"Rear","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$12,612.70 – $13,243.34","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/51d3d2c469a7b8675c070b4c3b00c9cf.pdf","sourceUrl":"https://www.se.com/ie/en/product/LV846555/circuit-breaker-frame-masterpact-mtz2-25h10-fixed-for-micrologic-x-2500a-50ka-1150vac-icu-4p/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV846555/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV846555","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV846555 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}