{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV847110","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV847110","canonicalUrl":"https://aoctrl.com/schneider/LV847110","factsUrl":"https://aoctrl.com/api/mcp/products/LV847110","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPact MTZ1, fixed circuit breaker, 3P, 630 A at 40 °C, H1 42 kA 415 V AC, push-button control, without control unit.","salesMarkdown":"The LV847110 is a Schneider Electric MasterPact MTZ1 fixed-mount circuit breaker, 3-pole, rated 630 A at 40 °C. That 630 A continuous current is the In — the breaker carries that load without tripping under normal conditions. The H1 performance level gives you 42 kA ultimate breaking capacity (Icu) at 415 V AC, which is the same 42 kA you get at 440 V, 500 V, and 690 V — the breaker doesn't derate its interrupting rating across the common industrial voltage range. That matters for panel coordination: if your fault current at the bus is, say, 35 kA, this breaker clears it without upstream intervention. Selectivity Category B means it's designed for full discrimination with downstream devices — a short on a branch won't take the main breaker out. The short-time withstand (Icw) is 42 kA for 1 second — that's the current it can carry for that duration while the downstream breaker clears a fault, essential for selective coordination studies. Fixed-mount version — bolts to a base plate or rails (mounting support listed as rails and base plate). The connection pitch is 70 mm, and both upside and downside connections accept front or rear terminations. That rear-connection option is useful when you're feeding a busbar stack behind the panel and don't want cable loops in front. Fine inside a locked panel; not for outdoor or washdown locations. Altitude derating starts above 2000 m — if you're installing at 3000 m, you'll need to reduce the continuous current per the manufacturer's curve. Also compliant with IEC 61557-12 for measuring equipment. Electrical durability: 6000 cycles at 440 V AC under AC-3 motor-switching duty, 3000 cycles at 690 V AC. Mechanical durability is 12,500 cycles with periodic preventive maintenance.","metaTitle":"Schneider Electric LV847110 MasterPact MTZ1 3P 630A Circuit","metaDescription":"Schneider Electric LV847110 MasterPact MTZ1 fixed circuit breaker, 630 A at 40 °C, 3-pole, H1 42 kA breaking capacity at 415 V AC. Active production, sourced to order. IEC 60947-2.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"209 mm","Range":"MasterPacT","Width":"276 mm","title":"LV847110","Height":"301 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12","description":"Circuit breaker Masterpact MTZ1 06H1, 630 A, 3P fixed, without Micrologic","Control type":"Push-button","Control unit":"Without control unit","Product name":"MasterPact MTZ1","Mounting mode":"Fixed","Sensor rating":"400 A 630 A","lifecycle_stage":"current","Connection pitch":"70 mm","Mounting support":"Rails Base plate","Performance type":"H1 42 kA 415 V AC","Pollution degree":"3 conforming to IEC 60947-1","Device short name":"MTZ1 06 H1","Poles description":"3P","Upside connection":"Front Rear","Device application":"Power distribution protection","Operating altitude":"0...2000 m without derating 2000...5000 m with derating","[In] rated current":"630 A at 40 °C","Downside connection":"Front Rear","Selectivity category":"Category B","Electrical durability":"3000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23A: 3000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23A: 6000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3","Maximum breaking time":"25 ms","Mechanical durability":"12500 cycles with periodic preventive maintenance","Power dissipation in W":"30 W","IP degree of protection":"IP30 conforming to EN 60529","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Maximum closing response time":"50 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"42 kA at 220/415 V AC 50/60 Hz 42 kA at 440 V AC 50/60 Hz 42 kA at 500/525 V AC 50/60 Hz 42 kA at 660/690 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"12 kV","[Icw] rated short-time withstand current":"42 kA 0.5 s 42 kA 1 s 24 kA 3 s","[Icm] rated short-circuit making capacity":"88 kA 220/415 V AC at 50/60 Hz 88 kA 440 V AC at 50/60 Hz 88 kA 500/525 V AC at 50/60 Hz 88 kA 660/690 V AC at 50/60 Hz","[Icu] rated ultimate short-circuit breaking capacity":"42 kA at 220/415 V AC 50/60 Hz 42 kA at 440 V AC 50/60 Hz 42 kA at 500/525 V AC 50/60 Hz 42 kA at 660/690 V AC 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$2,460.13 – $2,583.12","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/22201b9063cf068d46c6d6951594c3b5.pdf","sourceUrl":"https://www.se.com/vn/en/product/LV847110/circuit-breaker-masterpact-mtz1-06h1-630-a-3p-fixed-without-micrologic/"},"ai":{"faq":[{"question":"How do I get current pricing and availability for LV847110?","answer":"Submit an RFQ. We source this breaker to order and confirm current pricing and availability at quote time."},{"question":"What is LV847110's breaking capacity at 415 V AC?","answer":"The ultimate breaking capacity (Icu) is 42 kA at 415 V AC, and the service breaking capacity (Ics) is the same 42 kA — no derating across the 220-690 V range."},{"question":"What compliance documentation does this brand provide for LV847110?","answer":"The breaker is designed to EN/IEC 60947-1, EN/IEC 60947-2, and IEC 61557-12. It carries a suitability-for-isolation marking per EN/IEC 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV847110","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV847110 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}