{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV847115","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV847115","canonicalUrl":"https://aoctrl.com/schneider/LV847115","factsUrl":"https://aoctrl.com/api/mcp/products/LV847115","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPacT MTZ1, LV847115, fixed 4P circuit breaker, 630 A at 40 °C, H1 42 kA 415 V AC, Category B, IP30.","salesMarkdown":"## 630 A fixed-mount breaker for main distribution The Schneider Electric LV847115 is a MasterPact MTZ1 fixed circuit breaker rated 630 A at 40 °C, 4 poles, with H1 performance level delivering 42 kA Ics at 415 V AC. Category B selectivity means it coordinates with downstream breakers to isolate faults without blacking out the entire bus. The 42 kA Ics holds across the full voltage range up to 690 V AC — no derating curve to watch at higher voltages. Rated insulation voltage is 1000 V AC, impulse withstand 12 kV, and the breaker meets EN/IEC 60947-2 including Annex H for power distribution protection. Fixed-mount design — no draw-out cradle. Mounts on rails or base plate with a 70 mm connection pitch. Front and rear connection options on both upside and downside give flexibility for busbar or cable entry. Neutral position is left, standard for 4-pole distribution panels. Dimensions: 346 mm wide, 301 mm high, 209 mm deep. IP30 enclosure protection — suitable for enclosed switchboards, not open outdoor mounting. ## Breaking performance and durability Rated service breaking capacity (Ics) is 42 kA at every standard voltage: 220/415 V, 440 V, 500/525 V, and 660/690 V AC. Short-time withstand (Icw) holds 42 kA for 0.5 s or 1 s, 24 kA for 3 s — useful for selective coordination with downstream feeders. Making capacity (Icm) reaches 88 kA peak across the same voltage range. Mechanical durability is 12,500 cycles with periodic preventive maintenance. Electrical durability varies by voltage and duty: 3,000 cycles at 690 V AC, 6,000 cycles at 440 V AC under AC-23A or AC-3 conditions. Maximum breaking time 25 ms, closing response 50 ms.","metaTitle":"Schneider Electric LV847115 MasterPact MTZ1 630A 4P Circuit","metaDescription":"Schneider Electric LV847115 MasterPact MTZ1 630A 4P fixed circuit breaker. 42 kA Ics at 415 V AC, H1 performance, current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"209 mm","Range":"MasterPacT","Width":"346 mm","title":"LV847115","Height":"301 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12","description":"Circuit breaker frame, MasterPact MTZ1 06H1 fixed for MicroLogic X, 630A, 42kA/415VAC (Icu), 4P","Control type":"Push-button","Control unit":"Without control unit","Product name":"MasterPact MTZ1","Mounting mode":"Fixed","Sensor rating":"400 A 630 A","lifecycle_stage":"current","Connection pitch":"70 mm","Mounting support":"Rails Base plate","Neutral position":"Left","Performance type":"H1 42 kA 415 V AC","Pollution degree":"3 conforming to IEC 60947-1","Device short name":"MTZ1 06 H1","Poles description":"4P","Upside connection":"Front Rear","Device application":"Power distribution protection","Operating altitude":"0...2000 m without derating 2000...5000 m with derating","[In] rated current":"630 A at 40 °C","Downside connection":"Front Rear","Selectivity category":"Category B","Electrical durability":"3000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23A: 3000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23A: 6000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3","Maximum breaking time":"25 ms","Mechanical durability":"12500 cycles with periodic preventive maintenance","Power dissipation in W":"30 W","IP degree of protection":"IP30 conforming to EN 60529","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Maximum closing response time":"50 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"42 kA at 220/415 V AC 50/60 Hz 42 kA at 440 V AC 50/60 Hz 42 kA at 500/525 V AC 50/60 Hz 42 kA at 660/690 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"12 kV","[Icw] rated short-time withstand current":"42 kA 0.5 s 42 kA 1 s 24 kA 3 s","[Icm] rated short-circuit making capacity":"88 kA 220/415 V AC at 50/60 Hz 88 kA 440 V AC at 50/60 Hz 88 kA 500/525 V AC at 50/60 Hz 88 kA 660/690 V AC at 50/60 Hz","[Icu] rated ultimate short-circuit breaking capacity":"42 kA at 220/415 V AC 50/60 Hz 42 kA at 440 V AC 50/60 Hz 42 kA at 500/525 V AC 50/60 Hz 42 kA at 660/690 V AC 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$3,247.26 – $3,409.64","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a5d6a04b12fb0268f3448416ad60418d.pdf","sourceUrl":"https://www.se.com/th/en/product/LV847115/circuit-breaker-frame-masterpact-mtz1-06h1-fixed-for-micrologic-x-630a-42ka-415vac-icu-4p/"},"ai":{"faq":[{"question":"Where can I buy LV847115 and how do I get a price?","answer":"The LV847115 is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time."},{"question":"What is the closest alternative to LV847115 in the MasterPact family?","answer":"Within the MasterPact MTZ1 fixed-mount range, the closest alternative would be a different H1 performance level or a 3-pole variant. No direct pin-compatible drop-in exists with identical 630 A 4P H1 fixed configuration — verify coordination and mounting before substituting."},{"question":"What compliance documentation does this breaker carry?","answer":"The LV847115 complies with EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H, and IEC 61557-12. It is suitable for isolation per EN/IEC 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV847115","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV847115 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}