{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV847200","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV847200","canonicalUrl":"https://aoctrl.com/schneider/LV847200","factsUrl":"https://aoctrl.com/api/mcp/products/LV847200","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPacT, MasterPact MTZ1, LV847200, drawout circuit breaker, 3P, 630 A, H1 42 kA 415 V AC.","salesMarkdown":"The LV847200 is a Schneider Electric MasterPact MTZ1 drawout circuit breaker, 3-pole, rated 630 A at 40 °C. The Icw of 42 kA for 1 second confirms it withstands delayed-tripping coordination schemes common in selectivity studies. Drawout mounting means the breaker chassis stays wired to the bus while the removable cradle isolates for maintenance or swap — no need to disconnect power cables. Category B selectivity and suitability for isolation (per EN/IEC 60947-2) mean it can serve as the main incoming device in a distribution board where coordination with downstream breakers is required. ## Integration notes The breaker ships without a control unit (specified separately). Mounting support options include rails or a base plate. IP30 enclosure protection is standard; for panel environments with higher dust or moisture ingress, consider an enclosure upgrade. Power dissipation is 55 W — factor this into enclosure thermal calculations, especially in dense switchboards where multiple breakers stack. Altitude derating applies above 2000 m. Electrical durability is 6000 cycles at 440 V AC (AC-23A) and 3000 cycles at 690 V AC; mechanical durability is 12,500 cycles with periodic preventive maintenance. Maximum breaking time is 25 ms, closing response time 50 ms.","metaTitle":"Schneider Electric LV847200 MasterPact MTZ1 630A Drawout, 42","metaDescription":"Schneider Electric LV847200 MasterPact MTZ1 H1 3P drawout circuit breaker, 630 A rated current, 42 kA Icu/Ics at 415 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Voltage":"690 V AC 50/60 Hz","IP Rating":"IP30","Application":"Power distribution protection","Control Type":"Push-button","Product Status":"Active","Terminal Pitch":"70 mm","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"1000 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front Rear","Electrical Life Cycles":"3000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23 A: 3000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23 A: 6000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3","Mechanical Life Cycles":"12500 cycles with periodic preventive maintenance","Connection Surface Bottom":"Front Rear","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$2,448.29","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4452f8867f9bee87b04bf7830189a8c6.pdf","sourceUrl":"https://www.se.com/th/en/product/LV847200/circuit-breaker-frame-masterpact-mtz1-06h1-drawout-for-micrologic-x-630a-42ka-415vac-icu-3p/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV847200/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV847200","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV847200 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}