{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV847207","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV847207","canonicalUrl":"https://aoctrl.com/schneider/LV847207","factsUrl":"https://aoctrl.com/api/mcp/products/LV847207","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPact MTZ1, LV847207, drawout circuit breaker, 4P, 630 A at 40 °C, performance 150 kA at 415 V AC, IEC 60947-2.","salesMarkdown":"The Schneider Electric LV847207 is a MasterPact MTZ1 drawout circuit breaker rated 630 A at 40 °C, with an performance class delivering 150 kA Ics at 415 V AC. It's a 4-pole unit (neutral left) in a drawout chassis, designed for main or feeder protection in power distribution. Key specs: rated insulation voltage 1000 V AC, operational voltage 690 V AC, impulse withstand 12 kV. The Icw is 10 kA for 0.5 s, and the Icm making capacity hits 330 kA at 415 V. Breaking time maxes at 9 ms, closing at 50 ms. Electrical durability: 3000 cycles at 690 V AC-23A, 6000 at 440 V. Mechanical durability is 12,500 cycles with periodic maintenance. Drawout mounting means the breaker chassis stays wired to the bus; the moving portion pulls out for maintenance or swap without disturbing connections. Mounts on rails or base plate with a 70 mm connection pitch. Dimensions with chassis: 291 mm deep, 358 mm wide, 322 mm high. Without chassis: 207.5 mm deep, 306.5 mm wide, 259.5 mm high. Plan for the full chassis footprint in the switchgear lineup. ## Compliance & Lifecycle Power dissipation is 115 W at rated current — factor that into enclosure cooling. Control is push-button type; this variant ships without a control unit (Micrologic trip unit ordered separately).","metaTitle":"Schneider Electric LV847207 MasterPact MTZ1 Drawout Circuit","metaDescription":"Schneider Electric LV847207 MasterPact MTZ1 drawout circuit breaker, 630 A rated at 40 °C, 150 kA Ics at 415 V AC. Current production, sourced to order. IEC 60947-2.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"Drawout circuit breaker with chassis: 291 mm Drawout circuit breaker without chassis: 207.5 mm","Range":"MasterPacT","Width":"Drawout circuit breaker with chassis: 358 mm Drawout circuit breaker without chassis: 306.5 mm","title":"LV847207","Height":"Drawout circuit breaker with chassis: 322 mm Drawout circuit breaker without chassis: 259.5 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12","description":"Circuit breaker frame, MasterPact MTZ1 06L1 drawout for MicroLogic X, 630A, 150kA/415VAC (Icu), 4P","Control type":"Push-button","Control unit":"Without control unit","Product name":"MasterPact MTZ1","Mounting mode":"Drawout","Sensor rating":"400 A 630 A","lifecycle_stage":"current","Connection pitch":"70 mm","Mounting support":"Rails Base plate","Neutral position":"Left","Performance type":"L1 150 kA 415 V AC","Pollution degree":"3 conforming to IEC 60947-1","Device short name":"MTZ1 06 L1","Poles description":"4P","Upside connection":"Front Rear","Device application":"Power distribution protection","Operating altitude":"0...2000 m without derating 2000...5000 m with derating","[In] rated current":"630 A at 40 °C","Downside connection":"Front Rear","Selectivity category":"Category A","Electrical durability":"AC-23A: 3000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23A: 6000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 2000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 3000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2","Maximum breaking time":"9 ms","Mechanical durability":"12500 cycles with periodic preventive maintenance","Power dissipation in W":"115 W","IP degree of protection":"IP30 conforming to EN 60529","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Maximum closing response time":"50 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"150 kA at 220/415 V AC 50/60 Hz 130 kA at 440 V AC 50/60 Hz 100 kA at 500/525 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"12 kV","[Icw] rated short-time withstand current":"10 kA 0.5 s","[Icm] rated short-circuit making capacity":"330 kA 220/415 V AC at 50/60 Hz 286 kA 440 V AC at 50/60 Hz 220 kA 500/525 V AC at 50/60 Hz 52 kA 660/690 V AC at 50/60 Hz","Integrated instantaneous protection (DIN in kA peak)":"5.67...6.93 kA","[Icu] rated ultimate short-circuit breaking capacity":"150 kA at 220/415 V AC 50/60 Hz 130 kA at 440 V AC 50/60 Hz 100 kA at 500/525 V AC 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$5,125.22","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f48f2d349a164dc54699c31005335ada.pdf","sourceUrl":"https://www.se.com/th/en/product/LV847207/circuit-breaker-frame-masterpact-mtz1-06l1-drawout-for-micrologic-x-630a-150ka-415vac-icu-4p/"},"ai":{"faq":[{"question":"What is the closest alternative to LV847207 in the MasterPact family?","answer":"Within the MasterPact MTZ1 range, the closest sibling would be a different performance class or amperage rating — same drawout frame, same 4-pole footprint, but with a lower or higher interrupting capacity or current rating. The LV847207 is the 630 A variant; an MTZ1 with a different sensor rating (e.g., 400 A) or performance level (H1, H2) would be the parametric alternative."},{"question":"What compliance documentation does Schneider provide for LV847207?","answer":"The breaker is certified to EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H, and IEC 61557-12. It carries a suitability-for-isolation mark per IEC 60947-2. Standard documentation includes a declaration of conformity; specific RoHS/REACH declarations are available on request with the order."},{"question":"Where can I buy LV847207 and how is it quoted?","answer":"LV847207 is sourced and quoted to order against an RFQ through independent industrial distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm offer."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV847207","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV847207 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}