{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV847287WW","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV847287WW","canonicalUrl":"https://aoctrl.com/schneider/LV847287WW","factsUrl":"https://aoctrl.com/api/mcp/products/LV847287WW","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPacT MicroLogic 7.0 Xi control unit, LV847287WW, wired control, LCD display, LSIV protection, 3P 4P poles, 400-3200 A trip unit ratings.","salesMarkdown":"The Schneider Electric LV847287WW is a MicroLogic 7.0 Xi control unit for MasterPacT circuit breakers. It's the brain of the breaker — handling protection, metering, and communication in one package. This is the wired-control variant with an LCD display (128 x 96 pixels) that shows current, voltage, power, energy, harmonics, and event logs. The trip unit ratings span 400 A through 3200 A, so it fits a wide range of distribution frames. ## Protection and metering depth Protection functions are LSIV: long-time overload (ANSI 49), short-time short-circuit (ANSI 51), instantaneous short-circuit (ANSI 50), and earth-leakage (ANSI 51G). The earth-leakage path is built in — no external module needed. Thermal memory is included, so the trip curve accounts for prior heating when re-closing after a fault. That matters for motor and transformer feeders where repeated overloads degrade insulation before the next trip. Metering accuracy is class 1 for active energy, class 0.5 for voltage, and class 5 for current THD. Voltage measurement covers 208-828 V phase-to-phase and 120-480 V phase-to-neutral at 50/60 Hz. The unit logs min/max values, event and alarm logs, and time-stamped data — useful for post-event analysis without a separate power monitor. ## Standards and deployment context Rated to IEC 60947-2 (circuit breakers), IEC 61010-1 (measurement equipment), and IEC 60092-202 (marine electrical systems). Overvoltage category IV and pollution degree 3 — it's designed for main distribution panels, not just sub-feeds. Indoor use only; not approved for wet locations. Operating altitude up to 5000 m with voltage derating to 560 V AC above 2000 m. EMC compliance covers IEC 61000-4-2 through -4-6 (ESD, radiated, fast transient, surge, conducted RF) and CISPR 22 Class A conducted and radiated emissions.","metaTitle":"Schneider LV847287WW MicroLogic 7.0 Xi Control Unit, MasterP","metaDescription":"Schneider Electric LV847287WW MicroLogic 7.0 Xi control unit for MasterPacT breakers. LSIV protection, LCD display, 400-3200 A trip ratings. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Poles":"3","Voltage":"600 V AC, +/- 10 %","Application":"Equipment protection, monitoring and control","Control Type":"Wired control","Display Type":"LCD display - 128 x 96 pixels","Product Status":"Active","Trip Unit Type":"Electronic","Pollution Degree":"3 conforming to IEC 60947-1","Temp Operating Max":"70 °C","Temp Operating Min":"-35 °C","Main Product Or Component Type":"Control unit","Ambient Air Temperature Operation":"-25...70 °C (operating) -35 °C (for start-up of product)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4faa0a8eca3d0d1e39240f52cbefd3d9.pdf","sourceUrl":"https://www.se.com/ae/en/product/LV847287WW/micrologic-7-0xi-control-unit-no-wireless-masterpact-mtz1-mtz2-fixed-circuit-breakers-lsiv-protections/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV847287WW/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV847287WW","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV847287WW when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}