{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV847600","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV847600","canonicalUrl":"https://aoctrl.com/schneider/LV847600","factsUrl":"https://aoctrl.com/api/mcp/products/LV847600","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPacT, MicroLogic 2.0 X electronic control unit, LI protection, LCD display 128x96 pixels, energy metering, 4P 3P pole configuration.","salesMarkdown":"The Schneider Electric LV847600 is a MicroLogic 2.0 X electronic control unit for the MasterPacT range of air circuit breakers. It provides LI protection — long-time and instantaneous short-circuit protection per ANSI 50 and ANSI 49 — plus comprehensive energy metering and system diagnostics. This is the brain that sits on the breaker, not the breaker itself. You pair it with a MasterPacT frame rated from 400 A up to 6300 A, depending on the frame size (MTZ1, MTZ2, or MTZ3). It's an electronic trip unit (not thermal-magnetic), so it gives you adjustable long-time delay in 0.5 s steps and a full set of protection curves you can tune on-site. Measurement voltage range is 208…828 V phase-to-phase and 120…480 V phase-to-neutral — so it meters on both wye and delta configurations. Pole configuration is listed as 4P 3P, meaning the unit supports both 3-pole and 4-pole breaker frames. The neutral protection setting is configurable: 1 x Ir (4P 4d), 0.5 x Ir (4P 3d + N/2), 1.6 x Ir (4P 3d + OSN), or no protection (4P 3d). That matters when you're retrofitting a 3-pole breaker into a 4-pole installation or vice versa. Accuracy on current measurements is ±0.5 % across the full range (40…1600 x 1.2 A for MTZ1, up to 80…6300 x 1.2 A for MTZ3). Voltage accuracy is also ±0.5 %. That's Class 0.5 metering for voltage and Class 1 for active energy — good enough for submetering and energy allocation, though not utility-billing grade. It measures everything you'd expect from a power meter: phase currents, neutral current, ground fault current, all three phase-to-phase and phase-to-neutral voltages, active/reactive/apparent power and energy, power factor, frequency, THD, and unbalance. Demand values for current and power are logged. This control unit mounts directly onto the MasterPacT breaker frame — it's not a standalone device. The breaker itself is panel-mounted, typically in a switchboard or motor control center. Communication is via Bluetooth 4.0 LE (30 kbit/s), NFC (28.8 kbaud), and USB (115 kbaud). No Ethernet or fieldbus module on this variant — you'd step up to a MicroLogic 5.0 or 6.0 for that. The Bluetooth link is handy for commissioning with a tablet or phone; the USB port is for local configuration and firmware updates. The LCD display is 128 x 96 pixels — small but readable for local readings and alarm summaries. It shows real-time metering, trip cause, breaker health state, and event logs. ## Standards and environmental limits Compliant with EN/IEC 60947-2 (low-voltage switchgear), EN/IEC 60092-202 (marine electrical installations), EN/IEC 60947-1, EN/IEC 60255-1 (measuring relays), and EN/IEC 61010-1 (safety requirements for electrical equipment). Overvoltage category IV per IEC 61010-1 — suitable for main distribution panels. Operating temperature range is -25…70 °C, with start-up capability down to -35 °C. Relative humidity up to 95 % at 55 °C. Maximum operating altitude is 5000 m with voltage derating above 2000 m (560 V AC at altitude).","metaTitle":"Schneider Electric LV847600 MicroLogic 2.0 X Control Unit, M","metaDescription":"Schneider Electric LV847600 MicroLogic 2.0 X electronic control unit for MasterPacT breakers. LI protection, LCD display, energy metering. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Poles":"4P 3P","Range":"MasterPacT","title":"LV847600","Standards":"EN/IEC 60947-2 EN/IEC 60092-202 EN/IEC 60947-1 EN/IEC 60255-1 EN/IEC 61010-1","description":"MicroLogic 2.0X control unit, MasterPact MTZ","Display type":"LCD display - 128 x 96 pixels","Network type":"AC","Metering type":"Current I1, I2, I3, Iavg RMS Neutral current IN RMS Ground fault current Ig RMS Voltage V12, V23, V31, VLLavg RMS Voltage V1N, V2N, V3N, VLNavg RMS Active power P, P1, P2, P3 total Reactive power Q, Q1, Q2, Q3 total Apparent power S, S1, S2, S3 total Power factor Active energy Ep IN/OUT/tot Reactive energy Eq IN/OUT/tot Apparent energy Es IN/OUT/tot Demand current I1, I2, I3, In, Iavg Demand power P, Q, S Frequency Phase sequence Earth leakage current Total current harmonic distortion THD (I) Total voltage harmonic distortion THD (V) Unbalance current Unbalance voltage","Accuracy class":"Class 5: total current harmonic distortion THD (I) Class 0.5: unbalance voltage Class 1: active and reactive energy by pulse counting (+/- W.h, +/- VAR.h) Class 2: total voltage harmonic distortion THD (V)","Data recording":"Time stamping Data logs Event logs Alarm logs Maintenance logs Min/max of instantaneous values","Thermal memory":"Yes","Protection type":"Instantaneous short-circuit protection conforming to ANSI 50 Overload (long time) conforming to ANSI 49","lifecycle_stage":"current","Pollution degree":"3 conforming to IEC 60947-1","Trip unit rating":"400 A 630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A 4000 A 5000 A 6300 A","Device short name":"MicroLogic 2.0 X","Energy management":"Measurement ,active, reactive and apparent energy Measurement ,electrical network Measurement ,energy","Mounting location":"Indoor use only","Network frequency":"50/60 Hz","Relative humidity":"95 % at 55 °C conforming to IEC 60068-2-30","Device application":"Equipment protection, monitoring and control","Operating altitude":"<= 5000 m with operational voltage derating 560 V AC","Measurement voltage":"208...828 V AC 50/60 Hz phase to phase 120...480 V AC 50/60 Hz phase to neutral","Type of measurement":"Power meter","Measurement accuracy":"Current I1, I2, I3, Iavg, Idemand for MTZ1: +/- 0.5 % 40...1600 x 1.2 A Current I1, I2, I3, Iavg, Idemand for MTZ2: +/- 0.5 % 40...4000 x 1.2 A Current I1, I2, I3, Iavg, Idemand for MTZ3: +/- 0.5 % 80...6300 x 1.2 A Neutral current IN: +/- 1 % Ground fault current Ig: +/- 5 % Voltage V12, V23, V31, VLLavg: +/- 0.5 % 208...690 x 1.2 V Voltage V1N, V2N, V3N, VLNavg: +/- 0.5 % 120...400 x 1.2 V Active power P, P1, P2, P3, Pdemand: +/- 1 % Reactive power Q, Q1, Q2, Q3, Qdemand: +/- 2 % Apparent power S, S1, S2, S3, Sdemand: +/- 1 % Power factor: +/- 2 % Active energy Ep IN/OUT/tot: +/- 1 % Reactive energy Ep IN/OUT/tot: +/- 2 % Apparent energy Es IN/OUT/tot: +/- 1 % Frequency: +/- 0.005 Hz Earth leakage current: +/- 10 % Unbalance current: +/- 0.5 %","Measurement category":"Category IV conforming to IEC 61010-2-30","Overvoltage category":"IV conforming to IEC 61010-1","Trip unit technology":"Electronic","Product or component type":"Control unit","Neutral protection setting":"1 x Ir (4P 4d) 0.5 x Ir (4P 3d + N/2) 1.6 x Ir (4P 3d + OSN) No protection (4P 3d)","Circuit breaker application":"Distribution IEC standard","Communication port protocol":"Bluetooth 4.0 LE peer to peer 30 kbit/s NFC peer to peer 28800 bauds conforming to ISO 15963 USB peer to peer 115 kbauds","Frequency measurement range":"40...70 Hz","Protected poles description":"3P 3d 4P 3d 4P 3d + N/2 4P 4d 4P 3d + OSN","Environmental characteristic":"Wet location not approved for use conforming to IEC 61010-1","Electromagnetic compatibility":"Electrostatic discharge immunity test conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test conforming to IEC 61000-4-5 Conducted RF disturbances conforming to IEC 61000-4-6 Conducted and radiated emissions A conforming to CISPR 22","Trip unit protection functions":"LI","[Ue] rated operational voltage":"690 V AC, +/- 10 %","Long time delay adjustment type":"Adjustable in step of 0.5 s","Zone selective interlocking ZSI":"Without","Network and machine diagnosis type":"System (HMI) health state overview: circuit breaker health state Contacts state: circuit breaker health state MicroLogic service life: circuit breaker health state Tripping cause indication: circuit breaker tripping cause Identification card: diagnostic data Configured alarms synthesis: diagnostic data Monitored function: diagnostic data Operation: diagnostic data MicroLogic test: test Protection test: test Selectivity test: test Trip context information: crisis management Operation: advanced diagnostic Breaker service life: circuit breaker health state","Ambient air temperature for operation":"-25...70 °C (operating) -35 °C (for start-up of product)","[Tr] Long-Time Delay Adjustment Range":"12.5...600 s at 1.5 x Ir 0.5...24 s at 6 x Ir 0.7...16.6 s at 7.2 x Ir","[Ir] long time pick-up adjustment range":"0.4...1 x In adjustable in step of 1 A","Instantaneous pick-up adjustment type Ii":"Adjustable","[Ii] instantaneous pick-up adjustment range":"1.5...10 x Ir adjustable in step of 0.5 x Ir with embedded HMI 1.5...10 x Ir adjustable in step of 0.1 x Ir with Ecoreach software or MasterPact MTZ mobile app","[Li Mode] Instantaneous Delay Adjustment Range":"20 ms in standard"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f4ddafa8a575957e4b8a38c753723a34.pdf","sourceUrl":"https://www.se.com/sg/en/product/LV847600/micrologic-2-0x-control-unit-masterpact-mtz/"},"ai":{"faq":[{"question":"What is the closest alternative to LV847600 in the MicroLogic family?","answer":"The closest peer is the MicroLogic 5.0 X (LV847700), which adds Modbus communication and a more advanced protection set. The 2.0 X is the basic electronic trip unit with LI protection only — no Ethernet, no zone selective interlocking. If you need fieldbus integration, step up to the 5.0 X; if you only need adjustable electronic protection and local metering, the 2.0 X is the right fit."},{"question":"What compliance documentation does this part carry?","answer":"It is compliant with EN/IEC 60947-2, EN/IEC 60092-202 (marine), EN/IEC 60947-1, EN/IEC 60255-1, and EN/IEC 61010-1. Overvoltage category IV. EMC compliance includes electrostatic discharge, electromagnetic fields, fast transients, surge immunity (1.2/50 µs), and conducted RF disturbances per the IEC 61000-4-x series, plus conducted and radiated emissions Class A per CISPR 22."},{"question":"Where can I buy LV847600 and get current pricing?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV847600","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV847600 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}