{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV847604","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV847604","canonicalUrl":"https://aoctrl.com/schneider/LV847604","factsUrl":"https://aoctrl.com/api/mcp/products/LV847604","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPacT MicroLogic 7.0 X control unit, LV847604, electronic trip unit with LSIV protection, LCD display, 4P 3P poles, rated for 400–3200 A frames.","salesMarkdown":"## What this control unit does The LV847604 is a MicroLogic 7.0 X electronic control unit for Schneider MasterPacT circuit breakers. It's the brain that handles equipment protection, monitoring, and control inside the breaker — not a standalone device. You slot it into a compatible MasterPacT frame (trip unit ratings from 400 A up to 3200 A) and it takes over the trip logic, metering, and communications. Protection functions are LSIV: long-time overload (ANSI 49), instantaneous short-circuit (ANSI 50), short-time short-circuit (ANSI 51), and earth-leakage (ANSI 51G). That covers the full selectivity stack for a distribution feeder — you can coordinate downstream breakers with the short-time delay and ZSI (zone selective interlocking) to clear faults fast without tripping the whole bus. It measures everything you'd expect from a power meter: per-phase and average RMS current, neutral and ground fault current, phase-to-phase and phase-to-neutral voltage, active/reactive/apparent power, power factor, energy in/out/total, frequency, THD for current and voltage, unbalance, and demand values. Accuracy on current and voltage is ±0.5 %, active energy ±1 % — Class 1 for billing-grade energy logging. Mounts inside the MasterPacT breaker — no DIN rail, no separate enclosure. The 128 x 96 pixel LCD gives you local readout of all metered values and event logs without needing to plug in a laptop. Communication ports are Bluetooth 4.0 LE (30 kbit/s), NFC (28.8 kbaud), and USB (115 kbaud) for local configuration and data pull. No onboard Ethernet or fieldbus — that comes via a separate communication module on the breaker. Indoor use only, wet locations not approved. Operating altitude up to 5000 m with voltage derating above 2000 m (560 V AC at max altitude).","metaTitle":"Schneider LV847604 MicroLogic 7.0 X Control Unit, MasterPacT","metaDescription":"Schneider Electric LV847604 MicroLogic 7.0 X control unit for MasterPacT breakers. LSIV protection, LCD display, IEC 60947 compliant. Current lifecycle. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Poles":"4P 3P","Range":"MasterPacT","title":"LV847604","Standards":"EN/IEC 60947-1 EN/IEC 60092-202 EN/IEC 60255-1 EN/IEC 60947-2 EN/IEC 61010-1","description":"MicroLogic 7.0X control unit, MasterPact MTZ","Display type":"LCD display - 128 x 96 pixels","Network type":"AC","Metering type":"Current I1, I2, I3, Iavg RMS Neutral current IN RMS Ground fault current Ig RMS Voltage V12, V23, V31, VLLavg RMS Voltage V1N, V2N, V3N, VLNavg RMS Active power P, P1, P2, P3 total Reactive power Q, Q1, Q2, Q3 total Apparent power S, S1, S2, S3 total Power factor Active energy Ep IN/OUT/tot Reactive energy Eq IN/OUT/tot Apparent energy Es IN/OUT/tot Demand current I1, I2, I3, In, Iavg Demand power P, Q, S Frequency Phase sequence Earth leakage current Total current harmonic distortion THD (I) Total voltage harmonic distortion THD (V) Unbalance current Unbalance voltage","Accuracy class":"Class 5: total current harmonic distortion THD (I) Class 0.5: unbalance voltage Class 1: active and reactive energy by pulse counting (+/- W.h, +/- VAR.h) Class 2: total voltage harmonic distortion THD (V)","Data recording":"Maintenance logs Min/max of instantaneous values Time stamping Data logs Event logs Alarm logs","Thermal memory":"Yes","Protection type":"Overload protection (long time) conforming to ANSI 49 Instantaneous short-circuit protection conforming to ANSI 50 Short time short-circuit protection conforming to ANSI 51 Earth-leakage protection conforming to ANSI 51G","lifecycle_stage":"current","Pollution degree":"3 conforming to IEC 60947-1","Trip unit rating":"400 A 630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A","Device short name":"MicroLogic 7.0 X","Energy management":"Measurement ,active, reactive and apparent energy Measurement ,electrical network Measurement ,energy","Mounting location":"Indoor use only","Network frequency":"50/60 Hz","Relative humidity":"95 % at 55 °C conforming to IEC 60068-2-30","Device application":"Equipment protection, monitoring and control","Operating altitude":"<= 5000 m with operational voltage derating 560 V AC","Measurement voltage":"208...828 V AC 50/60 Hz phase to phase 120...480 V AC 50/60 Hz phase to neutral","Type of measurement":"Power meter","Measurement accuracy":"Current I1, I2, I3, Iavg, Idemand for MTZ1: +/- 0.5 % 40...1600 x 1.2 A Current I1, I2, I3, Iavg, Idemand for MTZ2: +/- 0.5 % 40...4000 x 1.2 A Current I1, I2, I3, Iavg, Idemand for MTZ3: +/- 0.5 % 80...6300 x 1.2 A Neutral current IN: +/- 1 % Ground fault current Ig: +/- 5 % Voltage V12, V23, V31, VLLavg: +/- 0.5 % 208...690 x 1.2 V Voltage V1N, V2N, V3N, VLNavg: +/- 0.5 % 120...400 x 1.2 V Active power P, P1, P2, P3, Pdemand: +/- 1 % Reactive power Q, Q1, Q2, Q3, Qdemand: +/- 2 % Apparent power S, S1, S2, S3, Sdemand: +/- 1 % Power factor: +/- 2 % Active energy Ep IN/OUT/tot: +/- 1 % Reactive energy Ep IN/OUT/tot: +/- 2 % Apparent energy Es IN/OUT/tot: +/- 1 % Frequency: +/- 0.005 Hz Earth leakage current: +/- 10 % Unbalance current: +/- 0.5 %","Measurement category":"Category IV conforming to IEC 61010-2-30","Overvoltage category":"IV conforming to IEC 61010-1","Trip unit technology":"Electronic","Earth-leakage protection":"With","Product or component type":"Control unit","Neutral protection setting":"1 x Ir (4P 4d) 0.5 x Ir (4P 3d + N/2) 1.6 x Ir (4P 3d + OSN) No protection (4P 3d)","Circuit breaker application":"Distribution IEC standard","Communication port protocol":"Bluetooth 4.0 LE peer to peer 30 kbit/s NFC peer to peer 28800 bauds conforming to ISO 15963 USB peer to peer 115 kbauds","Frequency measurement range":"40...70 Hz","Protected poles description":"3P 3d 4P 3d 4P 3d + N/2 4P 4d 4P 3d + OSN","Environmental characteristic":"Wet location not approved for use conforming to IEC 61010-1","Electromagnetic compatibility":"Electrostatic discharge immunity test conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test conforming to IEC 61000-4-5 Conducted RF disturbances conforming to IEC 61000-4-6 Conducted and radiated emissions A conforming to CISPR 22","Trip unit protection functions":"LSIV","[Ue] rated operational voltage":"600 V AC, +/- 10 %","Long time delay adjustment type":"Adjustable in step of 0.5 s","Zone selective interlocking ZSI":"With","Short-time delay adjustment type":"Adjustable","Network and machine diagnosis type":"System (HMI) health state overview: circuit breaker health state Contacts state: circuit breaker health state MicroLogic service life: circuit breaker health state Tripping cause indication: circuit breaker tripping cause Identification card: diagnostic data Configured alarms synthesis: diagnostic data Monitored function: diagnostic data Operation: diagnostic data MicroLogic test: test Protection test: test Selectivity test: test Trip context information: crisis management Operation: advanced diagnostic Breaker service life: circuit breaker health state","Ambient air temperature for operation":"-25...70 °C (operating) -35 °C (for start-up of product)","[Tr] Long-Time Delay Adjustment Range":"12.5...600 s at 1.5 x Ir 0.5...24 s at 6 x Ir 0.7...16.6 s at 7.2 x Ir","[Ir] long time pick-up adjustment range":"0.4...1 x In adjustable in step of 1 A","[Tsd] Short-Time Delay Adjustment Range":"0.1...0.4 s I²t=on 0...0.4 s I²t=off","Instantaneous pick-up adjustment type Ii":"Adjustable","[Isd] short-time pick-up adjustment range":"1.5...10 x Ir adjustable in step of 0.5 x Ir with embedded HMI 1.5...10 x Ir adjustable in step of 0.1 x Ir with Ecoreach software or MasterPact MTZ mobile app","[Ii] instantaneous pick-up adjustment range":"2...15 x In adjustable in step of 0.5 x In with embedded HMI 2...15 x In adjustable in step of 0.1 x In with Ecoreach software or MasterPact MTZ mobile app Ii enable on/off","[Li Mode] Instantaneous Delay Adjustment Range":"0 ms in fast 20 ms in standard","Residual earth-leakage time delay adjustment type":"Adjustable","[IΔn] residual earth-leakage sensitive adjustment":"0.5...30 A adjustable in step of 0.1 A","[Δt] residual earth-leakage time delay adjustment":"60...800 ms resettable time 140...1000 ms break time"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$5,896.07","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/57e7bab0a520caf605bfdcb093a721d2.pdf","sourceUrl":"https://www.se.com/za/en/product/LV847604/micrologic-7-0x-control-unit-masterpact-mtz/"},"ai":{"faq":[{"question":"What protection functions does LV847604 provide?","answer":"LSIV: long-time overload (ANSI 49), instantaneous short-circuit (ANSI 50), short-time short-circuit (ANSI 51), and earth-leakage (ANSI 51G). It also includes zone selective interlocking (ZSI) for coordinated fault clearing."},{"question":"What trip unit ratings are compatible with LV847604?","answer":"It's designed for MasterPacT frames with trip unit ratings of 400 A, 630 A, 800 A, 1000 A, 1250 A, 1600 A, 2000 A, 2500 A, and 3200 A. The control unit itself doesn't set the rating — it adapts to the breaker frame's current sensor."},{"question":"What compliance standards does LV847604 meet?","answer":"Certified to EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60092-202 (marine), EN/IEC 60255-1, and EN/IEC 61010-1. EMC compliance per IEC 61000-4-2/3/4/5/6 and CISPR 22 Class A conducted/radiated emissions."},{"question":"Where can I buy LV847604 and get current pricing?","answer":"Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV847604","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV847604 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}