{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV848067","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV848067","canonicalUrl":"https://aoctrl.com/schneider/LV848067","factsUrl":"https://aoctrl.com/api/mcp/products/LV848067","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPact MTZ2, LV848067, fixed-mount air circuit breaker, 4P, 2000 A at 40 °C, H2 100 kA at 415 V AC, without control unit.","salesMarkdown":"The Schneider Electric LV848067 is a MasterPact MTZ2 20 H2 fixed-mount air circuit breaker, 4-pole, rated 2000 A at 40 °C. The 2000 A sensor rating means the breaker's electronic trip unit reads current through that window; the frame itself handles the full 2000 A continuous without derating up to 40 °C ambient. This is a power distribution protection device, not a motor-circuit breaker. The 4-pole version with neutral on the right suits TN-S or TN-C-S systems where you switch the neutral. That's the ultimate short-circuit capacity — the breaker can interrupt one fault at that level and still be serviceable afterward. The service breaking capacity Ics matches Icu at 415 V (100 kA) and at 440 V (100 kA), meaning after clearing a fault at those voltages the breaker is rated to carry full current again. At 690 V, Ics drops to 85 kA. The making capacity Icm hits 220 kA at 415 V — that's the peak let-through the contacts must close onto and latch against. For selective coordination, the short-time withstand Icw is 85 kA for 0.5 s and 1 s, and 75 kA for 3 s, which gives downstream breakers time to clear a fault before this upstream device trips. Maximum breaking time is 25 ms, closing response 70 ms. The 12 kV impulse withstand covers surge coordination per IEC 60947-1. ## Environmental limits and durability Altitude: full rating up to 2000 m, derated above that to 5000 m. Electrical durability varies by duty: 8000 cycles at 440 V AC under EN/IEC 60947-2, 6000 cycles at 690 V AC under the same standard, and 6000 to 8000 cycles for AC-23A switching duties per EN/IEC 60947-3. Power dissipation is 250 W — factor that into enclosure ventilation or air conditioning for a multi-breaker lineup.","metaTitle":"Schneider Electric LV848067 MasterPact MTZ2 20 H2, 2000 A, 4","metaDescription":"Schneider Electric LV848067 MasterPact MTZ2 circuit breaker, 2000 A rated current, 4 poles, H2 100 kA at 415 V AC, fixed mounting. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"300 mm","Width":"537 mm","Height":"352 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP30","Application":"Power distribution protection","Control Type":"Push-button","Product Status":"Active","Terminal Pitch":"115 mm","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"1000 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front Rear","Connection Surface Bottom":"Front Rear","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/98e24ae25d80455b901162a3da33a1e6.pdf","sourceUrl":"https://www.se.com/au/en/product/LV848067/circuit-breaker-frame-masterpact-mtz2-20h2-fixed-for-micrologic-x-2000a-100ka-415vac-icu-4p-right-neutral/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV848067/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV848067","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV848067 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}