{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV848105","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV848105","canonicalUrl":"https://aoctrl.com/schneider/LV848105","factsUrl":"https://aoctrl.com/api/mcp/products/LV848105","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPact MTZ3 63 H2, LV848105, fixed-mount air circuit breaker, 4P, 6300 A at 40 °C, H2 150 kA at 415 V AC, rear connection.","salesMarkdown":"The LV848105 is a Schneider Electric MasterPact MTZ3 63 H2 air circuit breaker — fixed-mount, 4-pole, rated 6300 A at 40 °C. Category B selectivity (EN/IEC 60947-2) means the breaker coordinates with downstream devices so only the faulted branch opens, keeping the rest of the plant live. Rated insulation voltage is 1000 V AC, operational voltage 690 V AC. Maximum breaking time is 25 ms, closing response 80 ms. Power dissipation sits at 650 W, so panel ventilation needs to handle that heat load at full rating. This is a rear-connected, fixed-mount breaker with push-button control and no integrated control unit — it's a bare power switching and protection device, meant to be paired with a separate trip unit (Micrologic X or similar) for adjustable protection settings. The 997 mm width, 352 mm height, and 300 mm depth define the mounting footprint on rails or base plate. ## Deployment context — where this breaker lives The LV848105 is a fixed-mount air breaker for main or tie positions in low-voltage switchgear. It's not a plug-in or draw-out unit — once bolted to the busbars via rear connections, it stays. The 230 mm connection pitch and right-side neutral position are fixed; panel layout needs to accommodate that. IP30 protection means it's for indoor, dry environments only — no washdown, no outdoor exposure. Operating altitude is 0–2000 m without derating; above that, up to 5000 m, derate per the manufacturer's curve. The 650 W dissipation at full load means forced ventilation or a larger enclosure volume if the breaker is in a compact lineup.","metaTitle":"LV848105 MasterPact MTZ3 63 H2, 6300 A 150 kA","metaDescription":"Schneider Electric LV848105 MasterPact MTZ3 63 H2 air circuit breaker. 6300 A at 40 °C, 150 kA Ics at 415 V AC. Category B selectivity. Current production. Sourced to order against","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"300 mm","Width":"997 mm","Height":"352 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP30","Application":"Power distribution protection","Control Type":"Push-button","Product Status":"Active","Terminal Pitch":"230 mm","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"1000 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Rear","Connection Surface Bottom":"Rear","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4ed98ec974ef55f6b787a07742f925b3.pdf","sourceUrl":"https://www.se.com/ie/en/product/LV848105/circuit-breaker-mtz3-63h2-6300-a-4p-fixed-right-neutral-w-o-micrologic/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV848105/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV848105","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV848105 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}