{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV848181","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV848181","canonicalUrl":"https://aoctrl.com/schneider/LV848181","factsUrl":"https://aoctrl.com/api/mcp/products/LV848181","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPacT MTZ2, LV848181, fixed circuit breaker, 4P, 3200 A at 40 °C, H2 100 kA 415 V AC, push-button control, IP30.","salesMarkdown":"## MasterPact MTZ2 3200 A — fixed-mount power breaker The LV848181 is a Schneider Electric MasterPact MTZ2 fixed circuit breaker, 4-pole, rated 3200 A at 40 °C. Selectivity category B confirms it is designed for full discrimination downstream, critical for a main breaker in a distribution panel where you want only the faulted branch to trip. ## Breaking performance and coordination Rated short-time withstand current (Icw) is 85 kA for 0.5 s and 1 s, 75 kA for 3 s. That Icw figure governs the breaker's ability to hold a fault while downstream breakers clear — essential for zone-selective interlocking schemes. Making capacity (Icm) peaks at 220 kA at 415 V AC, which is the peak asymmetrical current the breaker can close into and latch. Maximum breaking time is 25 ms, fast enough to limit let-through energy for cable and busbar protection. Fixed-mount design on rails or base plate. Connection pitch is 115 mm. Both upside and downside connections accept front or rear termination — rear connection is typical for switchboard busbar stabs; front connection suits cable-entry panels. Neutral position is right. Dimensions: 537 mm wide, 352 mm high, 300 mm deep. Panel cutout and busbar spacing must accommodate the fixed footprint — no slide-in cradle here. ## Environmental and operational limits Altitude derating: full rating up to 2000 m, derated above to 5000 m. IP30 enclosure means protection against tools >2.5 mm but not water — install in a clean, dry switchboard or enclosure. Power dissipation 420 W — factor into panel ventilation calculations.","metaTitle":"LV848181 MasterPact MTZ2 3200A Circuit Breaker, 100 kA","metaDescription":"Schneider Electric LV848181 MasterPact MTZ2 fixed circuit breaker, 3200 A rated current, 100 kA breaking capacity at 415 V AC. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"300 mm","Width":"537 mm","Height":"352 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP30","Application":"Power distribution protection","Control Type":"Push-button","Product Status":"Active","Terminal Pitch":"115 mm","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"1000 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front Rear","Mechanical Life Cycles":"20000 cycles with periodic preventive maintenance","Connection Surface Bottom":"Front Rear","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/06136f7e8349846abffeb36dba00f938.pdf","sourceUrl":"https://www.se.com/th/en/product/LV848181/circuit-breaker-frame-masterpact-mtz2-32h2-fixed-for-micrologic-x-3200a-100ka-415vac-icu-4p-right-neutral/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV848181/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV848181","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV848181 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}