{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV848193","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV848193","canonicalUrl":"https://aoctrl.com/schneider/LV848193","factsUrl":"https://aoctrl.com/api/mcp/products/LV848193","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPact MTZ2, LV848193, 4P fixed circuit breaker, 4000 A rated current, H1 66 kA at 415 V AC, push-button control, IP30.","salesMarkdown":"The LV848193 is a MasterPact MTZ2 4P fixed circuit breaker rated 4000 A at 40 °C, with an H1 performance class delivering 66 kA Ics across the full voltage range up to 690 V AC. Selectivity category B means it coordinates with downstream breakers for selective tripping — the faulted branch clears while upstream stays closed. Rated insulation voltage is 1000 V AC, impulse withstand 12 kV. The 66 kA Icw for 3 s means it can carry a short-circuit current for that duration without damage — critical for downstream coordination studies. Fixed mounting on rails or base plate. Dimensions: 537 mm wide × 352 mm high × 300 mm deep. Connection pitch 150 mm. Upside and downside connections both accept front or rear termination — panel layout flexibility for top-feed or bottom-feed bus runs. Neutral position on the right. IP30 enclosure protection; pollution degree 3 per IEC 60947-1. ## Durability and environmental range Mechanical durability 20,000 cycles with periodic preventive maintenance. Electrical durability: 6000 cycles AC-3 at 440/690 V, 5000 cycles at 440 V per EN/IEC 60947-2. Maximum breaking time 25 ms; closing response time 70 ms. Power dissipation 650 W at rated current — factor into enclosure thermal calculations. Altitude 0–2000 m without derating, 2000–5000 m with derating.","metaTitle":"LV848193 MasterPact MTZ2 4000 A Circuit Breaker, 66 kA","metaDescription":"LV848193 MasterPact MTZ2 4P fixed circuit breaker, 4000 A rated current, 66 kA Ics at 415 V AC. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"300 mm","Width":"537 mm","Height":"352 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP30","Application":"Power distribution protection","Control Type":"Push-button","Product Status":"Active","Terminal Pitch":"150 mm","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"1000 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front Rear","Mechanical Life Cycles":"20000 cycles with periodic preventive maintenance","Connection Surface Bottom":"Front Rear","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ec20185ceda2cca1777125192f27f5de.pdf","sourceUrl":"https://www.se.com/id/en/product/LV848193/circuit-breaker-frame-masterpact-mtz2-40h1-fixed-for-micrologic-x-4000a-66ka-415vac-icu-4p-right-neutral/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV848193/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV848193","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV848193 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}