{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV848195","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV848195","canonicalUrl":"https://aoctrl.com/schneider/LV848195","factsUrl":"https://aoctrl.com/api/mcp/products/LV848195","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPacT MTZ3, type MTZ3 50 H1, fixed-mount 4P circuit breaker, 5000 A at 40 °C, H1 100 kA 415 V AC performance class.","salesMarkdown":"## What the 5000 A and 100 kA ratings mean for your switchboard The LV848195 is a MasterPacT MTZ3 50 H1 fixed-mount circuit breaker rated 5000 A at 40 °C with an H1 performance class delivering 100 kA Icu at 415 V AC. That 100 kA holds across the full operating voltage range up to 690 V AC, so the breaker clears a fault at the same interrupting capacity whether it sits on a 415 V or 690 V bus. The Icw rating of 100 kA for 3 s means it withstands a delayed trip coordination window without damage — essential for selective coordination (Category B per IEC 60947-2) where downstream breakers clear first and this unit holds in. The 420 W power dissipation at rated current matters for enclosure thermal design — a switchboard housing this unit needs ventilation or forced cooling to stay within the -25 to 70 °C operating range. ## Standards compliance and isolation suitability ## Physical integration — fixed-mount, rear-connected, 4P Fixed-mount design with rear connection on both the line and load sides. The 997 mm width, 352 mm height, and 300 mm depth define the panel cutout and busbar layout. Connection pitch is 230 mm, which matches standard MasterPacT busbar systems. Mounting support is rails or base plate — the breaker bolts into a dedicated cradle, not a DIN rail. The neutral pole is on the right (4P, neutral right), so busbar phasing must follow that orientation. ## Durability and operating conditions Mechanical durability is 10,000 cycles with periodic preventive maintenance. Electrical durability under AC-3 switching duty is 6000 cycles at 440/690 V AC. IP30 protection means it is not washdown-rated — install inside a switchboard enclosure.","metaTitle":"Schneider Electric LV848195 MasterPacT MTZ3 50 H1, 5000 A, 1","metaDescription":"Schneider Electric LV848195 MasterPacT MTZ3 50 H1 circuit breaker, 5000 A rated current, H1 100 kA at 415 V AC. Current lifecycle status, sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"300 mm","Width":"997 mm","Height":"352 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP30","Application":"Power distribution protection","Control Type":"Push-button","Product Status":"Active","Terminal Pitch":"230 mm","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"1000 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Rear","Mechanical Life Cycles":"10000 cycles with periodic preventive maintenance","Connection Surface Bottom":"Rear","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cb1695a7df43e3e35eeadfceeff2f8aa.pdf","sourceUrl":"https://www.se.com/ie/en/product/LV848195/circuit-breaker-mtz3-50h1-5000-a-4p-fixed-right-neutral-w-o-micrologic/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV848195/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV848195","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV848195 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}