{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV848227","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV848227","canonicalUrl":"https://aoctrl.com/schneider/LV848227","factsUrl":"https://aoctrl.com/api/mcp/products/LV848227","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPacT MasterPact MTZ2, LV848227, drawout circuit breaker, 4P, 1000 A at 40 °C, H1 66 kA 415 V AC, EN/IEC 60947-2.","salesMarkdown":"The LV848227 is a MasterPact MTZ2 drawout circuit breaker rated 1000 A at 40 °C with an H1 performance class delivering 66 kA Ics across 220–690 V AC. Selectivity category B means the breaker has intentional short-time delay capability, so it coordinates selectively with downstream feeders — critical for a main or tie breaker in a switchboard where you want only the faulted branch to open. The drawout mounting allows the breaker to be racked out for maintenance or replacement without disturbing the primary connections — standard for large switchgear where downtime on the bus is not acceptable. The chassis adds 103 mm to the depth (403 mm with chassis vs 300 mm without) and 63 mm to the width (556 mm vs 493 mm), so verify the cubicle depth before specifying. Mounting support options include rails or a base plate. Altitude rating is 0–2000 m without derating, 2000–5000 m with derating. IP30 protection means the breaker is protected against tools and wires greater than 2.5 mm — standard for enclosed switchgear; the enclosure itself provides the higher IP rating. Power dissipation is 150 W at rated current — account for this in the switchgear ventilation calculation. The control type is push-button and ships without a control unit — the Micrologic trip unit is ordered separately as a system component. Upside and downside connections are both available in front or rear configurations, with a connection pitch of 115 mm. Sensor rating options are 400 A, 630 A, 800 A, and 1000 A — the breaker frame accepts any of these, so the same LV848227 can be down-rated with a lower sensor if the load changes.","metaTitle":"LV848227 MasterPact MTZ2 Drawout Circuit Breaker, 1000 A, 66","metaDescription":"LV848227 MasterPact MTZ2 drawout circuit breaker, 1000 A rated current, H1 66 kA breaking capacity at 415 V AC. 4P, EN/IEC 60947-2. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"Drawout circuit breaker with chassis: 403 mm Drawout circuit breaker without chassis: 300 mm","Range":"MasterPacT","Width":"Drawout circuit breaker with chassis: 556 mm Drawout circuit breaker without chassis: 493 mm","title":"LV848227","Height":"Drawout circuit breaker with chassis: 439 mm Drawout circuit breaker without chassis: 300 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12","description":"Circuit breaker frame, MasterPact MTZ2 10H1 drawout for MicroLogic X, 1000A, 66kA/415VAC (Icu), 4P right neutral","Control type":"Push-button","Control unit":"Without control unit","Product name":"MasterPact MTZ2","Mounting mode":"Drawout","Sensor rating":"400 A 630 A 800 A 1000 A","lifecycle_stage":"current","Connection pitch":"115 mm","Mounting support":"Rails Base plate","Neutral position":"Right","Performance type":"H1 66 kA 415 V AC","Pollution degree":"3 conforming to IEC 60947-1","Device short name":"MTZ2 10 H1","Poles description":"4P","Upside connection":"Front Rear","Device application":"Power distribution protection","Operating altitude":"0...2000 m without derating 2000...5000 m with derating","[In] rated current":"1000 A at 40 °C","Downside connection":"Front Rear","Selectivity category":"Category B","Electrical durability":"10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23A: 10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23A: 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440/690 V AC 50/60 Hz conforming to EN/IEC 60947-3","Maximum breaking time":"25 ms","Mechanical durability":"25000 cycles with periodic preventive maintenance","Power dissipation in W":"150 W","IP degree of protection":"IP30 conforming to EN 60529","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"66 kA at 220/415 V AC 50/60 Hz 66 kA at 440 V AC 50/60 Hz 66 kA at 500/525 V AC 50/60 Hz 66 kA at 660/690 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"12 kV","[Icw] rated short-time withstand current":"66 kA 0.5 s 66 kA 1 s 36 kA 3 s","[Icm] rated short-circuit making capacity":"145 kA 220/415 V AC at 50/60 Hz 145 kA 440 V AC at 50/60 Hz 145 kA 500/525 V AC at 50/60 Hz 145 kA 660/690 V AC at 50/60 Hz","[Icu] rated ultimate short-circuit breaking capacity":"66 kA at 220/415 V AC 50/60 Hz 66 kA at 440 V AC 50/60 Hz 66 kA at 500/525 V AC 50/60 Hz 66 kA at 660/690 V AC 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/dc9c0a7f09b6ee4a05b89566f75f3d77.pdf","sourceUrl":"https://www.se.com/id/en/product/LV848227/circuit-breaker-frame-masterpact-mtz2-10h1-drawout-for-micrologic-x-1000a-66ka-415vac-icu-4p-right-neutral/"},"ai":{"faq":[{"question":"What are the key ratings for LV848227?","answer":"The LV848227 is rated 1000 A at 40 °C with an H1 performance class delivering 66 kA Ics at 220–690 V AC. It is a 4-pole drawout breaker with a rated insulation voltage of 1000 V AC and operational voltage of 690 V AC. The impulse withstand is 12 kV."},{"question":"What is the breaking capacity of LV848227 at 415 V?","answer":"The service breaking capacity Ics is 66 kA at 220/415 V AC 50/60 Hz. The making capacity Icm at that voltage is 145 kA. The short-time withstand Icw is 66 kA for 0.5 s or 1 s."},{"question":"What is the depth of LV848227 with and without chassis?","answer":"With the drawout chassis, the depth is 403 mm; without the chassis, the breaker body is 300 mm deep. Width is 556 mm with chassis, 493 mm without. Height is 439 mm with chassis, 300 mm without."},{"question":"What standards does LV848227 comply with?","answer":"The LV848227 complies with EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H, and IEC 61557-12. It is suitable for isolation per EN/IEC 60947-2 and rated for pollution degree 3."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV848227","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV848227 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}