{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV848334","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV848334","canonicalUrl":"https://aoctrl.com/schneider/LV848334","factsUrl":"https://aoctrl.com/api/mcp/products/LV848334","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPacT MTZ3, LV848334, 4P drawout circuit breaker, 5000 A at 40 °C, H1 100 kA 415 V AC, Category B.","salesMarkdown":"The Schneider Electric LV848334 is a MasterPact MTZ3 drawout circuit breaker, 4-pole, rated 5000 A at 40 °C. Isolation-rated per EN/IEC 60947-2, so it doubles as a visible-break disconnect when racked out. That 100 kA Ics holds across the full voltage band — 220/415 V, 440 V, 500/525 V, and 660/690 V AC — so you don't lose breaking capacity on higher-voltage feeds. Short-time withstand (Icw) is 100 kA for 3 seconds, which is what lets it coordinate with downstream breakers on a high-fault bus. Making capacity (Icm) at 220 kA means it can close into a bolted fault without welding contacts. Maximum breaking time is 25 ms, closing response 80 ms — fast enough to limit arc-flash energy on a main breaker. Power dissipation at rated load is 670 W, so factor that into your enclosure ventilation calc, especially in a row of drawout cassettes. ## Drawout mounting and panel fit This is a drawout breaker — the moving portion racks into a fixed chassis (sold separately). With chassis, the envelope is 403 mm deep × 1016 mm wide × 479 mm high. Without chassis, 300 mm deep × 838 mm wide × 300 mm high. Connection pitch is 230 mm, rear-connected both top and bottom. Mounts on rails or a base plate. IP30 front face — suitable for indoor switchgear, not washdown areas. Also complies with IEC 61557-12 for insulation monitoring. Pollution degree 3 (industrial environment). Insulation voltage 1000 V AC, impulse withstand 12 kV. Altitude rated to 2000 m without derating, 2000–5000 m with derating.","metaTitle":"Schneider Electric LV848334 MasterPact MTZ3 5000A Drawout Br","metaDescription":"Schneider Electric LV848334 MasterPact MTZ3 4P drawout circuit breaker, 5000A rated current, H1 100kA at 415V AC, Category B. In current production, sourced to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Voltage":"690 V AC 50/60 Hz","IP Rating":"IP30","Application":"Power distribution protection","Control Type":"Push-button","Product Status":"Active","Terminal Pitch":"230 mm","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"1000 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Rear","Connection Surface Bottom":"Rear","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5e68b87dcc4f61b36a5aa5398ca02305.pdf","sourceUrl":"https://www.se.com/ae/en/product/LV848334/circuit-breaker-mtz3-50h1-5000-a-4p-drawout-right-neutral-w-o-micrologic/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV848334/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV848334","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV848334 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}