{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV848427","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV848427","canonicalUrl":"https://aoctrl.com/schneider/LV848427","factsUrl":"https://aoctrl.com/api/mcp/products/LV848427","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPact MTZ2 drawout circuit breaker, LV848427, 4P, 1000 A rated current, H2 100 kA breaking capacity at 415 V AC, Category B selectivity.","salesMarkdown":"The Schneider LV848427 is a MasterPact MTZ2 drawout circuit breaker, 4-pole, rated 1000 A at 40 °C. The H2 rating delivers 100 kA Icu at 415 V AC and 85 kA at 690 V AC. Short-time withstand (Icw) is 85 kA for 1 second, which covers delayed tripping for selective coordination. Making capacity (Icm) hits 220 kA at 415 V, handling the first asymmetric peak of a short circuit. ## Drawout construction and panel integration Drawout mounting means the breaker slides into a fixed chassis — the disconnect position isolates it for maintenance without unbolting power cables. With chassis, the unit is 403 mm deep, 556 mm wide, 439 mm tall. Without chassis, depth drops to 300 mm, width to 493 mm, height to 300 mm. Connection pitch is 115 mm; both front and rear connection are available. Mounts on rails or a base plate. IP30 protection per EN 60529. Rated insulation voltage 1000 V AC, operational voltage 690 V AC, impulse withstand 12 kV. Electrical durability is 10,000 cycles at 440 V and 690 V AC; mechanical durability 25,000 cycles with periodic preventive maintenance.","metaTitle":"Schneider LV848427 MasterPact MTZ2 1000A Drawout Breaker, 10","metaDescription":"Schneider LV848427 MasterPact MTZ2 drawout circuit breaker rated 1000 A at 40 °C, H2 100 kA breaking capacity at 415 V AC. Current production, sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"Drawout circuit breaker with chassis: 403 mm Drawout circuit breaker without chassis: 300 mm","Range":"MasterPacT","Width":"Drawout circuit breaker with chassis: 556 mm Drawout circuit breaker without chassis: 493 mm","title":"LV848427","Height":"Drawout circuit breaker with chassis: 439 mm Drawout circuit breaker without chassis: 300 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12","description":"Circuit breaker frame, MasterPact MTZ2 10H2 drawout for MicroLogic X, 1000A, 100kA/415VAC (Icu), 4P right neutral","Control type":"Push-button","Control unit":"Without control unit","Product name":"MasterPact MTZ2","Mounting mode":"Drawout","Sensor rating":"400 A 630 A 800 A 1000 A","lifecycle_stage":"current","Connection pitch":"115 mm","Mounting support":"Rails Base plate","Neutral position":"Right","Performance type":"H2 100 kA 415 V AC","Pollution degree":"3 conforming to IEC 60947-1","Device short name":"MTZ2 10 H2","Poles description":"4P","Upside connection":"Front Rear","Device application":"Power distribution protection","Operating altitude":"0...2000 m without derating 2000...5000 m with derating","[In] rated current":"1000 A at 40 °C","Downside connection":"Front Rear","Selectivity category":"Category B","Electrical durability":"10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23A: 10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23A: 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440/690 V AC 50/60 Hz conforming to EN/IEC 60947-3","Maximum breaking time":"25 ms","Mechanical durability":"25000 cycles with periodic preventive maintenance","Power dissipation in W":"150 W","IP degree of protection":"IP30 conforming to EN 60529","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz 85 kA at 500/525 V AC 50/60 Hz 85 kA at 660/690 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"12 kV","[Icw] rated short-time withstand current":"85 kA 0.5 s 85 kA 1 s 50 kA 3 s","[Icm] rated short-circuit making capacity":"220 kA 220/415 V AC at 50/60 Hz 220 kA 440 V AC at 50/60 Hz 187 kA 500/525 V AC at 50/60 Hz 187 kA 660/690 V AC at 50/60 Hz","Integrated instantaneous protection (DIN in kA peak)":"171...209 kA","[Icu] rated ultimate short-circuit breaking capacity":"100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz 85 kA at 500/525 V AC 50/60 Hz 85 kA at 660/690 V AC 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9b9a168bab837f7893631c036e52b2be.pdf","sourceUrl":"https://www.se.com/au/en/product/LV848427/circuit-breaker-frame-masterpact-mtz2-10h2-drawout-for-micrologic-x-1000a-100ka-415vac-icu-4p-right-neutral/"},"ai":{"faq":[{"question":"How do I get current pricing and availability for LV848427?","answer":"The LV848427 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is LV848427's breaking capacity at 415 V?","answer":"The H2 performance class delivers 100 kA Icu and 100 kA Ics at 415 V AC, 50/60 Hz."},{"question":"What standards does LV848427 comply with?","answer":"It complies with EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H, and IEC 61557-12. It is suitable for isolation per EN/IEC 60947-2."},{"question":"What is the depth of LV848427 with and without the chassis?","answer":"Drawout circuit breaker with chassis: 403 mm deep. Drawout circuit breaker without chassis: 300 mm deep."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV848427","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV848427 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}