{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV848427","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV848427","canonicalUrl":"https://aoctrl.com/schneider/LV848427","factsUrl":"https://aoctrl.com/api/mcp/products/LV848427","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPact MTZ2 drawout circuit breaker, LV848427, 4P, 1000 A rated current, H2 100 kA breaking capacity at 415 V AC, Category B selectivity.","salesMarkdown":"The Schneider LV848427 is a MasterPact MTZ2 drawout circuit breaker, 4-pole, rated 1000 A at 40 °C. The H2 rating delivers 100 kA Icu at 415 V AC and 85 kA at 690 V AC. Short-time withstand (Icw) is 85 kA for 1 second, which covers delayed tripping for selective coordination. Making capacity (Icm) hits 220 kA at 415 V, handling the first asymmetric peak of a short circuit. ## Drawout construction and panel integration Drawout mounting means the breaker slides into a fixed chassis — the disconnect position isolates it for maintenance without unbolting power cables. With chassis, the unit is 403 mm deep, 556 mm wide, 439 mm tall. Without chassis, depth drops to 300 mm, width to 493 mm, height to 300 mm. Connection pitch is 115 mm; both front and rear connection are available. Mounts on rails or a base plate. IP30 protection per EN 60529. Rated insulation voltage 1000 V AC, operational voltage 690 V AC, impulse withstand 12 kV. Electrical durability is 10,000 cycles at 440 V and 690 V AC; mechanical durability 25,000 cycles with periodic preventive maintenance.","metaTitle":"Schneider LV848427 MasterPact MTZ2 1000A Drawout Breaker, 10","metaDescription":"Schneider LV848427 MasterPact MTZ2 drawout circuit breaker rated 1000 A at 40 °C, H2 100 kA breaking capacity at 415 V AC. Current production, sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Voltage":"690 V AC 50/60 Hz","IP Rating":"IP30","Application":"Power distribution protection","Control Type":"Push-button","Product Status":"Active","Terminal Pitch":"115 mm","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"1000 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front Rear","Electrical Life Cycles":"10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23 A: 10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23 A: 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440/690 V AC 50/60 Hz conforming to EN/IEC 60947-3","Mechanical Life Cycles":"25000 cycles with periodic preventive maintenance","Connection Surface Bottom":"Front Rear","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9b9a168bab837f7893631c036e52b2be.pdf","sourceUrl":"https://www.se.com/au/en/product/LV848427/circuit-breaker-frame-masterpact-mtz2-10h2-drawout-for-micrologic-x-1000a-100ka-415vac-icu-4p-right-neutral/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV848427/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV848427","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV848427 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}