{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX0FF007","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX0FF007","canonicalUrl":"https://aoctrl.com/schneider/LX0FF007","factsUrl":"https://aoctrl.com/api/mcp/products/LX0FF007","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F series, LX0FF007 contactor coil, 127 V AC/DC control circuit, obsolete lifecycle.","salesMarkdown":"The LX0FF007 is a contactor coil from the Schneider Electric TeSys F range, designed to actuate the main contactor armature in TeSys F contactor assemblies. It operates on a 127 V control circuit, accepting both AC (50...400 Hz) and DC supply, making it flexible for panels with mixed control voltage sources. ## Key electrical characteristics Latching time is 35...40 ms, unlatching 50...100 ms. Coil resistance measures 11.61 Ω for the latching winding and 1788 Ω for the unlatching winding at 68 °F (20 °C). The high unlatching resistance indicates a separate hold-in winding or a pulse-operated unlatch circuit — common in TeSys F mechanically latched contactors where the unlatch coil only needs a brief pulse to release the armature. ## Mechanical ratings and duty cycle This duty cycle suits intermittent switching applications like conveyor start/stop or pump cycling, but not high-speed repetitive operations where a higher-rated coil would be needed.","metaTitle":"TeSys LX0FF007 Contactor Coil, 127 V AC/DC, Obsolete","metaDescription":"TeSys F LX0FF007 contactor coil, 127 V AC/DC control circuit. Obsolete — sourced to order against RFQ. 35-40 ms latching, 1 Mcycles mechanical durability.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Coil Voltage":"127 V AC 50...400 Hz 127 V DC","Operating Time":"35...40 ms latching 50...100 ms unlatching","Product Status":"Active","Control Circuit Type":"AC 50...400 Hz DC standard","Mechanical Life Cycles":"1 Mcycles","Main Product Or Component Type":"Contactor coil"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5ca1de6c0853c449400715f666f577f8.pdf","sourceUrl":"https://www.se.com/vn/en/product/LX0FF007/tesys-f-contactor-coil-lx0ff-127-v-ac-dc/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX0FF007/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX0FF007","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX0FF007 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}