{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX0FF056","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX0FF056","canonicalUrl":"https://aoctrl.com/schneider/LX0FF056","factsUrl":"https://aoctrl.com/api/mcp/products/LX0FF056","rawCanonicalId":null},"summary":{"shortDescription":"TeSys F, contactor coil, LX0FF056, 110 V DC low consumption, 35...40 ms latching 50...100 ms unlatching.","salesMarkdown":"## Coil for TeSys F contactor replacement The LX0FF056 is a replacement coil for TeSys F contactors, specified at 110 V DC low consumption control circuit. The latching time falls within 35 to 40 ms, and unlatching takes 50 to 100 ms — the asymmetry matters if your safety circuit timing relies on dropout speed. Coil resistance measures 23.37 Ohm latching and 706.44 Ohm unlatching at 20 °C, which lets you verify the winding integrity with a simple ohmmeter before installation. ## Control voltage limits and duty cycle At 110 V DC nominal, that means the coil holds in from roughly 93.5 V to 121 V DC. Maximum operating rate is 120 cycles per hour at 40 °C, with mechanical durability rated at 1 million cycles — per the datasheet, that's the mechanical life, not the electrical endurance under load.","metaTitle":"TeSys LX0FF056 Contactor Coil, 110 V DC Low Consumption","metaDescription":"TeSys F LX0FF056 contactor coil, 110 V DC low consumption. Active production. 35-40 ms latching, 50-100 ms unlatching. 23.37 Ohm latching resistance at 20 °C.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","title":"LX0FF056","description":"TeSys F - contactor coil - LX0FF - 110 V DC low consumption","Operating time":"35...40 ms latching 50...100 ms unlatching","lifecycle_stage":"current","Device short name":"LX0FF","Average resistance":"23.37 Ohm latching at 20 °C 706.44 Ohm unlatching at 20 °C","Control circuit type":"DC low consumption","Mechanical durability":"1 Mcycles","Maximum operating rate":"120 cyc/h 40 °C","Product or component type":"Contactor coil","[Uc] control circuit voltage":"110 V DC","Control circuit voltage limits":"Latching: 0.85...1.1 Uc Unlatching: 0.85...1.1 Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/65de24781b5e2772a0301d20764d73c3.pdf","sourceUrl":"https://www.se.com/th/en/product/LX0FF056/tesys-f-contactor-coil-lx0ff-110-v-dc-low-consumption/"},"ai":{"faq":[{"question":"What is the closest alternative to LX0FF056 in the TeSys F family?","answer":"Within the TeSys F range, the LX0FF056 is the specific 110 V DC low-consumption coil. Other voltage variants (e.g., 24 V DC, 48 V DC, 220 V DC) exist under different LX0FF order codes, but they are not pin-compatible substitutes — the coil voltage must match the contactor control circuit. No direct cross-reference to a different manufacturer's coil is documented."},{"question":"What are the key specifications for LX0FF056?","answer":"Control circuit voltage is 110 V DC low consumption. Operating time: 35 to 40 ms latching, 50 to 100 ms unlatching. Coil resistance: 23.37 Ohm latching, 706.44 Ohm unlatching at 20 °C. Mechanical durability: 1 million cycles. Maximum operating rate: 120 cycles per hour at 40 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX0FF056","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX0FF056 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}