{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX0FG058","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX0FG058","canonicalUrl":"https://aoctrl.com/schneider/LX0FG058","factsUrl":"https://aoctrl.com/api/mcp/products/LX0FG058","rawCanonicalId":null},"summary":{"shortDescription":"TeSys F, contactor coil, LX0FG058, 220 V DC low consumption, obsolete.","salesMarkdown":"The LX0FG058 is a TeSys F contactor coil from Schneider Electric, designed for 220 V DC low-consumption control circuits. It latches in 35–40 ms and unlatches in 50–100 ms, which matters when timing a contactor dropout sequence in a safety circuit or motor start scheme. Control voltage is 220 V DC, with a latching and unlatching tolerance of 0.85–1.1 Uc — so the coil holds in reliably between 187 V and 242 V DC. Below that range, expect dropout. Coil resistance is 102.44 Ω for the latching winding and 2378.62 Ω for the unlatching winding at 20 °C. That difference tells you the holding current is much lower than the pick-up current — typical for a DC low-consumption design that keeps heat down in the panel. That cycling limit is the real-world constraint for frequent jogging or inching applications — stay under 2 cycles per minute to avoid overheating the coil.","metaTitle":"TeSys LX0FG058 Contactor Coil, 220 VDC, Obsolete","metaDescription":"TeSys F LX0FG058 contactor coil, 220 V DC low consumption. Obsolete – sourced to order against RFQ. Operating time 35–40 ms latching, 50–100 ms unlatching.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","Operating time":"35...40 ms latching 50...100 ms unlatching","lifecycle_stage":"current","Device short name":"LX0FG","Average resistance":"102.44 Ohm latching at 20 °C 2378.62 Ohm unlatching at 20 °C","Control circuit type":"DC low consumption","Mechanical durability":"1 Mcycles","Maximum operating rate":"120 cyc/h 40 °C","Product or component type":"Contactor coil","[Uc] control circuit voltage":"220 V DC","Control circuit voltage limits":"Latching: 0.85...1.1 Uc Unlatching: 0.85...1.1 Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8c10bdd09da94ffabb2dab52a4971706.pdf","sourceUrl":"https://www.se.com/vn/en/product/LX0FG058/tesys-f-contactor-coil-lx0fg-220-v-dc-low-consumption/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX0FG058/alternatives.json"},"ai":{"faq":[{"question":"What is the control voltage and type for LX0FG058?","answer":"220 V DC, low-consumption design. Latching tolerance is 0.85–1.1 Uc (187–242 V DC)."},{"question":"What are the operating times for this coil?","answer":"Latching takes 35–40 ms; unlatching takes 50–100 ms."},{"question":"What is the mechanical durability and maximum cycling rate?","answer":"Rated for 1 million mechanical cycles, with a maximum operating rate of 120 cycles per hour at 40 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX0FG058","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX0FG058 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}