{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX0FH011","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX0FH011","canonicalUrl":"https://aoctrl.com/schneider/LX0FH011","factsUrl":"https://aoctrl.com/api/mcp/products/LX0FH011","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F contactor coil, LX0FH011, 415 V AC 50/60 Hz, obsolete lifecycle stage.","salesMarkdown":"The coil draws a latching resistance of 102.9 Ω and an unlatching resistance of 15006 Ω at 20 °C, with operating times of 50...100 ms for unlatching and 45...50 ms for latching. Control circuit voltage tolerance is 0.85...1.1 Uc for both latching and unlatching, meaning the coil holds in and drops out reliably across a 353...456 V AC window at the 415 V nominal. ## Mechanical and electrical endurance Rated for 1 million mechanical cycles and a maximum operating rate of 120 cycles per hour at 40 °C — sufficient for moderate-duty switching applications such as conveyor or pump control.","metaTitle":"TeSys LX0FH011 Contactor Coil, 415 V AC 50/60 Hz, Obsolete","metaDescription":"TeSys F contactor coil LX0FH011, 415 V AC 50/60 Hz control circuit. Obsolete — sourced to order against RFQ. Coil resistance 102.9 Ω latching, 15006 Ω unlatching at 20 °C.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Coil Voltage":"415 V AC 50/60 Hz","Operating Time":"50...100 ms unlatching 45...50 ms latching","Product Status":"Active","Control Circuit Type":"AC 50/60 Hz","Mechanical Life Cycles":"1 Mcycles","Main Product Or Component Type":"Contactor coil"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/de4c2bc053e34d98bd9ceecaeac035bd.pdf","sourceUrl":"https://www.se.com/ie/en/product/LX0FH011/tesys-f-contactor-coil-lx0fh-415-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX0FH011/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX0FH011","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX0FH011 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}