{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX0FH058","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX0FH058","canonicalUrl":"https://aoctrl.com/schneider/LX0FH058","factsUrl":"https://aoctrl.com/api/mcp/products/LX0FH058","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F, LX0FH058, contactor coil, 220 V DC low consumption, obsolete.","salesMarkdown":"The LX0FH058 is a replacement contactor coil for the TeSys F range, designed for 220 V DC low-consumption control circuits. It is the part that pulls the contactor in and holds it, so the operating time — 50 to 100 ms unlatching, 45 to 50 ms latching — governs how fast the main contacts close and open. That matters when you are coordinating with other devices in a motor starter or transfer scheme. Rated for 220 V DC control circuits, with a latching voltage tolerance of 0.85 to 1.1 Uc and the same for unlatching. That means the coil will reliably pick up and hold between about 187 V and 242 V DC. The average resistance is 97.89 ohms latching and 1344.46 ohms unlatching at 20 °C — the high unlatching resistance is characteristic of the low-consumption design, which keeps the holding power draw down once the contactor is sealed in.","metaTitle":"TeSys LX0FH058 Contactor Coil, 220 V DC Low Consumption, Obs","metaDescription":"TeSys F LX0FH058 contactor coil, 220 V DC low consumption, obsolete. Sourced to order against RFQ. Operating time 50-100 ms unlatching.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","Operating time":"50...100 ms unlatching 45...50 ms latching","lifecycle_stage":"current","Device short name":"LX0FH","Average resistance":"97.89 Ohm latching at 20 °C 1344.46 Ohm unlatching at 20 °C","Control circuit type":"DC low consumption","Mechanical durability":"1 Mcycles","Maximum operating rate":"120 cyc/h 40 °C","Product or component type":"Contactor coil","[Uc] control circuit voltage":"220 V DC","Control circuit voltage limits":"Latching: 0.85...1.1 Uc Unlatching: 0.85...1.1 Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/aadf05a49c2ad439d3875ea5754f952c.pdf","sourceUrl":"https://www.se.com/sg/en/product/LX0FH058/tesys-f-contactor-coil-lx0fh-220-v-dc-low-consumption/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX0FH058/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to LX0FH058 in the TeSys F family?","answer":"Schneider Electric has not published an official successor order code for this coil. For a replacement, you would need to cross-reference the contactor frame size and control voltage against the current TeSys F coil offering — the LX0FH058 is a 220 V DC low-consumption coil, so any substitute must match that voltage and the mechanical interface."},{"question":"What is the operating time of LX0FH058?","answer":"Unlatching time is 50 to 100 ms; latching time is 45 to 50 ms. These times affect coordination with other devices in the control circuit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX0FH058","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX0FH058 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}