{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX0FJ010","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX0FJ010","canonicalUrl":"https://aoctrl.com/schneider/LX0FJ010","factsUrl":"https://aoctrl.com/api/mcp/products/LX0FJ010","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F contactor coil, LX0FJ010, 380-400 V AC 50/60 Hz, active lifecycle.","salesMarkdown":"The LX0FJ010: The control circuit voltage is 380-400 V AC 50/60 Hz. That means the coil is designed for a line-to-line or line-to-neutral supply at those levels — common in European 400 V three-phase panels. The voltage limits are 0.85 to 1.1 times Uc for both latching and unlatching, so the coil holds in reliably down to about 323 V and up to 440 V. If your control voltage is 24 V DC or 230 V, this is not the coil you need. Operating time is 50-100 ms unlatching and 40-75 ms latching. That is typical for a contactor coil of this size — fast enough for motor starting and general switching, but not for high-speed applications like inverter bypass contactors that need sub-20 ms response. That rate is fine for most pump, fan, and conveyor duty; if you are cycling a load every 30 seconds continuously, you will exceed the rating. The coil resistance is 94.8 ohms for the latching winding and 9380 ohms for the unlatching winding at 20 °C. The high unlatching resistance means the holding current is low once the contactor is sealed — the coil driver only needs to supply a brief inrush for latching, then a much lower current to keep it closed. That is standard for AC-operated contactor coils with a separate unlatching (holding) circuit.","metaTitle":"TeSys LX0FJ010 Contactor Coil, 380-400 V AC, Active","metaDescription":"TeSys F LX0FJ010 contactor coil, 380-400 V AC 50/60 Hz control circuit. Active lifecycle. 1 Mcycles mechanical durability. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","title":"LX0FJ010","Category":"22341-CONTACTOR,D,K,&F ACCESS","description":"TeSys F - contactor coil - LX0FJ - 380...400 V AC","Operating time":"50...100 ms unlatching 40...75 ms latching","lifecycle_stage":"current","Device short name":"LX0FJ","Average resistance":"94.8 Ohm latching 68 °F (20 °C) 9380 Ohm unlatching 68 °F (20 °C)","Control circuit type":"AC 50/60 Hz","Mechanical durability":"1 Mcycles","Nbr. of units in pkg.":"1","Maximum operating rate":"120 cyc/h 104 °F (40 °C)","Product or Component Type":"Contactor coil","[Uc] control circuit voltage":"380...400 V AC 50/60 Hz","Control circuit voltage limits":"Latching: 0.85...1.1 Uc Unlatching: 0.85...1.1 Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0e06f0480a95d4fbf261e23b0ffac9d9.pdf","sourceUrl":"https://www.se.com/th/en/product/LX0FJ010/tesys-f-contactor-coil-lx0fj-380-400-v-ac/"},"ai":{"faq":[{"question":"What is the control voltage for this coil?","answer":"The control circuit voltage is 380-400 V AC 50/60 Hz. The coil operates within 0.85 to 1.1 times Uc for both latching and unlatching."},{"question":"What is the mechanical durability of this coil?","answer":"Mechanical durability is rated at 1 million cycles, with a maximum operating rate of 120 cycles per hour at 40 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX0FJ010","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX0FJ010 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}