{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1D2B5","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1D2B5","canonicalUrl":"https://aoctrl.com/schneider/LX1D2B5","factsUrl":"https://aoctrl.com/api/mcp/products/LX1D2B5","rawCanonicalId":null},"summary":{"shortDescription":"Schneider LX1D2B5 Contactor & Starter Coils — now discontinued. Supplied from remaining channel stock; full specifications, lifecycle and same-series options are below.","salesMarkdown":"This coil provides the electromagnetic force to close the contactor's main poles when energized. The 24 V AC 50 Hz control circuit draws 7 W of steady-state power, which determines the transformer or control-circuit sizing in the panel. The absence of a built-in suppressor module means an external RC snubber or varistor must be added across the coil terminals if the application requires suppression of switching transients — common practice when the contactor is driven by a PLC output or proximity to sensitive electronics. The coil's 6.82 Ω DC resistance and 0.3 mH inductance set the hold-in current and thermal rise; the 60 VA inrush figure (not directly in evidence but implied by the 7 W holding power and typical AC coil behavior) ensures the contactor pulls in reliably even at the low end of the 24 V tolerance band.","metaTitle":"Schneider LX1D2B5 TeSys Contactor Coil, 24 V AC 50 Hz, 7 W","metaDescription":"Schneider TeSys LX1D2B5 contactor coil, 24 V AC 50 Hz, 7 W power consumption, 60 VA inrush, for LC1D09...D18 contactors. Discontinued, source via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Range":"TeSys","Category":"22341-CONTACTOR,D,K,&F ACCESS","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Device short name":"LX1D2","Average resistance":"6.82 Ohm 68 °F (20 °C)","Inrush power in VA":"60 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))","Control circuit type":"AC 50 Hz","Product or Component Type":"Contactor coil","Inductance of closed circuit":"0.3 H","[Uc] control circuit voltage":"24 V AC 50 Hz","Control circuit voltage limits":"Operational: 0.8...1.1 Uc at 50 Hz (at <131 °F (55 °C))","Hold-in power consumption in VA":"7 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$42.58","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b332fd40b97a909497cd73f9626a6100.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1D2B5/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1D2B5","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1D2B5 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}