{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1D2FE7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1D2FE7","canonicalUrl":"https://aoctrl.com/schneider/LX1D2FE7","factsUrl":"https://aoctrl.com/api/mcp/products/LX1D2FE7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys D contactor coil, LX1D2FE7, 115 V AC 50/60 Hz, for 9..18 A contactors, obsolete.","salesMarkdown":"The LX1D2FE7 is a replacement coil for TeSys D contactors in the 9–18 A frame — the LX1D2 variant. It pulls 70 VA inrush at 50/60 Hz (cos φ 0.75) and holds at 8 VA (cos φ 0.3), both at 20 °C. Coil voltage is 115 V AC 50/60 Hz, with an operating band of 0.8 to 1.1 Uc below 55 °C. No built-in suppressor module, so you'll want an external RC snubber or varistor across the coil if the PLC output driving it is solid-state. This coil is marked obsolete by Schneider Electric. If you're kitting a spare for an existing panel, confirm the coil footprint and mounting match the LX1D2 armature before committing; the 115 V AC variant is common enough that a cross-reference exists in the aftermarket, but there's no single direct-replacement part number from Schneider. Mounts directly onto the TeSys D contactor magnet assembly — no DIN-rail space consumed beyond the contactor itself. The coil terminals accept the same quick-connect tabs as the contactor coil socket. If you're swapping a failed coil in a live panel, kill the control transformer first; the 70 VA inrush can weld a relay contact if the supply is hot-dropped.","metaTitle":"TeSys LX1D2FE7 Contactor Coil, 115 V AC, Obsolete","metaDescription":"TeSys D contactor coil LX1D2FE7, 115 V AC 50/60 Hz, for 9..18 A contactors. Obsolete — sourced to order against an RFQ. Inrush 70 VA, hold 8 VA.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Coil Voltage":"115 V AC 50/60 Hz","Product Status":"Active","Control Circuit Type":"AC at 50/60 Hz","Main Product Or Component Type":"Contactor coil"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9d9161517213c1f23a0ceab0158c1265.pdf","sourceUrl":"https://www.se.com/sg/en/product/LX1D2FE7/contactor-coil-tesys-d-lx1d2-115-v-ac-50-60-hz-for-9-18-a-contactor/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1D2FE7/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1D2FE7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1D2FE7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}