{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1D2L6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1D2L6","canonicalUrl":"https://aoctrl.com/schneider/LX1D2L6","factsUrl":"https://aoctrl.com/api/mcp/products/LX1D2L6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys LX1D2L6 contactor coil, 208 V AC 60 Hz, without built-in suppressor module, for 9 to 18 A contactors.","salesMarkdown":"## Lifecycle status and sourcing reality The LX1D2L6: This coil is a replacement part for TeSys D contactors in the 9 to 18 A frame — a common line-down spare in older panels. Sourcing is confirmed per RFQ; availability and pricing are verified at quote time through our independent distribution network. ## Coil ratings and fit for the contactor This voltage tolerance ensures reliable pick-up even on a lightly loaded control transformer. Inrush power is 70 VA at 60 Hz (cos φ 0.75), dropping to 7.5 VA hold-in (cos φ 0.3). The 16.6 H inductance of the closed circuit means the holding current is low, so the coil runs cool in continuous duty — important for densely packed panels where heat buildup is a concern. Average DC resistance is 417.8 Ω at 68 °F (20 °C). This is a useful check when verifying coil integrity with an ohmmeter during commissioning or troubleshooting. ## Coil technology and panel integration This coil is supplied without a built-in suppressor module. If the contactor is switched by a PLC output or a solid-state relay, an external RC snubber or varistor should be added across the coil to suppress back-EMF and protect the switching device. Part of the TeSys D range, the LX1D2L6 is a direct-fit replacement for the standard coil on 9 to 18 A TeSys D contactors. No mounting modification is needed — it clips onto the contactor magnet assembly in the same footprint as the original.","metaTitle":"Schneider Electric LX1D2L6 TeSys Contactor Coil","metaDescription":"Obsolete Schneider Electric LX1D2L6 TeSys contactor coil, 208 V AC 60 Hz, for 9 to 18 A contactors.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Device short name":"LX1D2","Average resistance":"417.8 Ohm 68 °F (20 °C)","Inrush power in VA":"70 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))","Control circuit type":"AC 60 Hz","Product or component type":"Contactor coil","Inductance of closed circuit":"16.6 H","[Uc] control circuit voltage":"208 V AC 60 Hz","Control circuit voltage limits":"Operational: 0.8...1.1 Uc at 60 Hz (at <131 °F (55 °C))","Hold-in power consumption in VA":"7.5 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$80.35","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/vn/en/product/LX1D2L6/tesys-d-contactor-coil-lx1d2-208-v-ac-60-hz-for-9-to-18-a-contactor/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1D2L6/alternatives.json"},"ai":{"faq":[{"question":"What is LX1D2L6's listed range (TeSys) on this component line?","answer":"The LX1D2L6 belongs to the TeSys D range of contactor coils, designed for 9 to 18 A TeSys D contactors."},{"question":"What is LX1D2L6's listed coil technology (Without built-in suppressor module) on this component line?","answer":"The LX1D2L6 is supplied without a built-in suppressor module. An external suppression device (RC snubber or varistor) is recommended when the coil is driven by a solid-state output."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1D2L6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1D2L6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}