{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1D2P5","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1D2P5","canonicalUrl":"https://aoctrl.com/schneider/LX1D2P5","factsUrl":"https://aoctrl.com/api/mcp/products/LX1D2P5","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys D, LX1D2P5 contactor coil, 230 V AC 50 Hz, for 9 to 18 A contactors.","salesMarkdown":"The Schneider Electric LX1D2P5 is a replacement contactor coil from the TeSys D range, part of the LX1D2 device family. It is designed for 230 V AC 50 Hz control circuits and mates with 9 to 18 A TeSys D contactors. The coil draws 60 VA inrush at 50 Hz (cos φ 0.75) and holds at 7 VA (cos φ 0.3), both measured at 68 °F (20 °C). The closed-circuit inductance is 25 H, and the average DC resistance is 649.7 Ω at the same temperature. Operational voltage limits are 0.8 to 1.1 Uc at 50 Hz, up to 131 °F (55 °C). The coil has no built-in suppressor module — an external RC snubber or varistor should be added across the coil terminals if driving from a PLC output or electronic controller. ## What to verify before ordering This coil is AC 50 Hz only — it will not hold in on a 60 Hz supply or DC control voltage. The 230 V rating is nominal; the 0.8 to 1.1 Uc operating range means it drops out below roughly 184 V and may overheat above 253 V. Because the coil lacks a built-in suppressor, any inductive kickback when de-energizing must be managed externally. A standard RC snubber (0.1 µF + 100 Ω) across the coil terminals protects nearby electronics and extends contactor life.","metaTitle":"Schneider LX1D2P5 TeSys D Contactor Coil, 230 V AC 50 Hz, Ob","metaDescription":"Schneider Electric LX1D2P5 TeSys D replacement contactor coil, 230 V AC 50 Hz for 9-18 A contactors. Obsolete — sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","Category":"22341-CONTACTOR,D,K,&F ACCESS","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Device short name":"LX1D2","Average resistance":"649.7 Ohm 68 °F (20 °C)","Inrush power in VA":"60 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))","Control circuit type":"AC 50 Hz","Product or Component Type":"Contactor coil","Inductance of closed circuit":"25 H","[Uc] control circuit voltage":"230 V AC 50 Hz","Control circuit voltage limits":"Operational: 0.8...1.1 Uc at 50 Hz (at <131 °F (55 °C))","Hold-in power consumption in VA":"7 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/30c8d7d5f6376c7ab69f00e68fc80624.pdf","sourceUrl":"https://www.se.com/vn/en/product/LX1D2P5/tesys-d-contactor-coil-lx1d2-230-v-ac-50-hz-for-9-to-18-a-contactor/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1D2P5/alternatives.json"},"ai":{"faq":[{"question":"What contactors does this coil fit?","answer":"The LX1D2P5 is a TeSys D replacement coil for 9 to 18 A contactors in the same range. It is part of the LX1D2 device family and uses a 230 V AC 50 Hz control circuit."},{"question":"Does this coil include a built-in surge suppressor?","answer":"No. The LX1D2P5 is specified without a built-in suppressor module. An external RC snubber or varistor should be added across the coil when switching with electronic controls."},{"question":"What is the operating voltage range for this coil?","answer":"The operational limits are 0.8 to 1.1 times the nominal control voltage (230 V AC) at 50 Hz, up to 131 °F (55 °C). That gives a working range of approximately 184 to 253 V AC."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1D2P5","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1D2P5 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}