{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1D2U7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1D2U7","canonicalUrl":"https://aoctrl.com/schneider/LX1D2U7","factsUrl":"https://aoctrl.com/api/mcp/products/LX1D2U7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys D LX1D2U7 contactor coil, 230-240 V AC 50/60 Hz, 645 ohm coil resistance, 70 VA inrush / 8 VA hold-in, for 9 to 18 A contactors.","salesMarkdown":"## What this coil fits and why the VA matters The LX1D2U7 is a replacement coil for TeSys D contactors rated 9 through 18 A — the LC1D09 through LC1D18 frame sizes. It pulls 70 VA inrush at pickup (cos φ 0.75) and settles to 8 VA sealed (cos φ 0.3). That inrush-to-hold ratio is typical for AC-operated contactor coils; the control transformer or PLC output driving it must supply the 70 VA peak without voltage sag, or the contactor may chatter on pull-in. Coil resistance measures 645 Ω at 20 °C, and the closed-circuit inductance is 25 H — the high inductance after the armature seats explains the low hold-in VA. ## Obsolete — sourcing path Schneider has marked the LX1D2U7 as obsolete. No official successor order code is listed on the manufacturer record. The coil is available through independent surplus and new-old-stock channels; quantities are lot-specific and confirmed at RFQ. For a panel with an existing TeSys D contactor needing a coil swap, the LX1D2U7 is the direct fit — same mechanical interface, same terminal layout. No pin-compatible alternative from Schneider has been published for this voltage variant.","metaTitle":"Schneider LX1D2U7 TeSys contactor coil, 230-240 VAC","metaDescription":"Schneider Electric LX1D2U7 TeSys D contactor coil, 230-240 VAC 50/60 Hz, for 9-18 A contactors. Obsolete — sourced to order. RFQ for availability.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","Category":"22341-CONTACTOR,D,K,&F ACCESS","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Device short name":"LX1D2","Average resistance":"645 Ohm 68 °F (20 °C)","Inrush power in VA":"70 VA 50/60 Hz cos phi 0.75 (at 68 °F (20 °C))","Control circuit type":"AC 50/60 Hz","Nbr. of units in pkg.":"1","Product or Component Type":"Contactor coil","Inductance of closed circuit":"25 H","[Uc] control circuit voltage":"240 V AC 60 Hz 230...240 V AC 50 Hz","Control circuit voltage limits":"Operational: 0.8...1.1 Uc at 50/60 Hz (at <131 °F (55 °C))","Hold-in power consumption in VA":"8 VA 50/60 Hz cos phi 0.3 (at 68 °F (20 °C))"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$32.00","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/id/en/product/LX1D2U7/tesys-d-contactor-coil-lx1d2-230240-v-ac-50-60-hz-for-9-to-18-a-contactor/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1D2U7/alternatives.json"},"ai":{"faq":[{"question":"What contactor does the LX1D2U7 coil fit?","answer":"It fits TeSys D contactors in the 9 to 18 A range — the LC1D09 through LC1D18 frame sizes. The coil voltage is 230-240 V AC 50/60 Hz."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1D2U7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1D2U7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}