{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1D2Y5","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1D2Y5","canonicalUrl":"https://aoctrl.com/schneider/LX1D2Y5","factsUrl":"https://aoctrl.com/api/mcp/products/LX1D2Y5","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys D LX1D2Y5 contactor coil, 220 V AC 50 Hz, 60 VA inrush, 7 VA hold-in.","salesMarkdown":"The LX1D2Y5 is a replacement coil for the TeSys D contactor range, designed for 220 V AC 50 Hz control circuits. It draws 60 VA inrush at pickup and settles to 7 VA holding — the inrush figure matters for transformer sizing in the control panel; a 60 VA surge on a small control transformer can drop the rail below the dropout threshold if the transformer is undersized. ## Voltage tolerance and fit The coil operates across 0.8 to 1.1 times Uc (176 to 242 V AC) at ambient up to 55 °C. That 0.8 lower limit is the practical dropout boundary — if your control voltage sags below 176 V during a downstream fault, the contactor drops out, which may be either a safety feature or a nuisance trip depending on the circuit design.","metaTitle":"Schneider Electric LX1D2Y5 TeSys D Contactor Coil, 220 V AC","metaDescription":"Replacement coil for TeSys D contactors. 220 V AC 50 Hz coil, 60 VA inrush, 7 VA hold-in. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Coil Type":"AC 50 Hz","Coil Voltage":"220 V AC 50 Hz","Product Status":"Active","Control Circuit Type":"AC","Main Product Or Component Type":"Contactor coil"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a2b3b0e7874312c47c9022577f145647.pdf","sourceUrl":"https://www.se.com/ie/en/product/LX1D2Y5/contactor-coil-tesys-d-lx1d-660-v-ac-50-hz/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1D2Y5/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1D2Y5","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1D2Y5 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}