{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1D6R6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1D6R6","canonicalUrl":"https://aoctrl.com/schneider/LX1D6R6","factsUrl":"https://aoctrl.com/api/mcp/products/LX1D6R6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca, LX1D6R6, contactor coil, 440 V AC 60 Hz, for 80 & 95 A contactors.","salesMarkdown":"## Part Identity and Fit The LX1D6R6 is a replacement coil from the Schneider TeSys Deca range, designed for 80 A and 95 A contactors in that family. It is a 440 V AC 60 Hz control circuit coil, the LX1D6 device short name variant, with a 392 Ohm average resistance at 68 °F (20 °C) and an inductance of 19 H when closed. This coil has no built-in suppressor module, so if your panel design requires a snubber or varistor across the coil terminals for noise suppression or to extend the life of the driving PLC output, you will need to add it externally. The heat dissipation runs 6 to 10 W at 50/60 Hz, which should be accounted for in the thermal budget of a tightly packed enclosure. ## Control Circuit and Performance Its operating limits at 60 Hz and below 131 °F (55 °C) are 0.85 to 1.1 Uc for pick-up, and drop-out occurs between 0.3 and 0.6 Uc. Inrush power is 220 VA at 60 Hz with a cos phi of 0.75, while hold-in power drops to 22 VA at 60 Hz with a cos phi of 0.3.","metaTitle":"TeSys LX1D6R6 Contactor Coil, 440 V AC 60 Hz, Obsolete","metaDescription":"Schneider TeSys LX1D6R6 contactor coil, 440 V AC 60 Hz, for 80 & 95 A contactors. Obsolete status; sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Range":"TeSys","title":"LX1D6R6","Category":"22341-CONTACTOR,D,K,&F ACCESS","description":"TeSys Deca - contactor coil - LX1D6 - 440 V AC 60 Hz for 80 & 95 A contactor","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Heat dissipation":"6...10 W 50/60 Hz","Device short name":"LX1D6","Average resistance":"392 Ohm 68 °F (20 °C)","Inrush power in VA":"220 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))","Control circuit type":"AC 60 Hz","Mechanical durability":"10 Mcycles","Nbr. of units in pkg.":"1","Maximum operating rate":"3600 cyc/h 140 °F (60 °C)","Product or Component Type":"Contactor coil","Inductance of closed circuit":"19 H","[Uc] control circuit voltage":"440 V AC 60 Hz","Control circuit voltage limits":"Drop-out: 0.3...0.6 Uc at 50/60 Hz (at Operational: 0.8...1.1 Uc at 50 Hz (at Operational: 0.85...1.1 Uc at 60 Hz (at <131 °F (55 °C))","Hold-in power consumption in VA":"22 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))","Ambient Air Temperature for Operation":"23...140 °F (-5...60 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a90054a705b1f37829325e983d725d22.pdf","sourceUrl":"https://www.se.com/us/en/product/LX1D6R6/tesys-deca-contactor-coil-lx1d6-440-v-ac-60-hz-for-80-95-a-contactor/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1D6R6/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to LX1D6R6?","answer":"No direct replacement order code is listed by the manufacturer. For a new design, you would need to select a current-production TeSys coil with the same voltage and contactor frame size. Contact us with your contactor model for a cross-reference."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1D6R6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1D6R6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}