{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1D6Z7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1D6Z7","canonicalUrl":"https://aoctrl.com/schneider/LX1D6Z7","factsUrl":"https://aoctrl.com/api/mcp/products/LX1D6Z7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca, contactor coil LX1D6Z7, 20 V AC 50/60 Hz, for 40 to 95 A contactor, obsolete.","salesMarkdown":"The LX1D6Z7 is a replacement coil for the TeSys Deca contactor range, sized for 40 to 95 A contactors and wound for 20 V AC 50/60 Hz control. This coil pulls 245 VA inrush at 60 Hz (cos φ 0.75) and holds at 26 VA (cos φ 0.3) — the inrush figure matters for sizing the control transformer feeding it, especially if several coils pull in simultaneously. It carries no built-in suppressor module, so you'll need an external RC snubber or varistor across the coil if the PLC output or relay driving it is solid-state or sensitive to back-EMF.","metaTitle":"Schneider TeSys LX1D6Z7 Contactor Coil, 20 VAC, Obsolete","metaDescription":"Schneider TeSys LX1D6Z7 contactor coil, 20 V AC 50/60 Hz for 40-95 A contactors. Obsolete status; sourced to order against RFQ. Inrush 245 VA.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","Category":"18401-WORLD SERVICE PARTS(CTR ACCESS)","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Device short name":"LX1D6","Inrush power in VA":"245 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C)) 245 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))","Control circuit type":"AC 50/60 Hz","Nbr. of units in pkg.":"1","Product or Component Type":"Contactor coil","[Uc] control circuit voltage":"20 V AC 50/60 Hz","Control circuit voltage limits":"Operational: 0.85...1.1 Uc at 50/60 Hz (at <131 °F (55 °C))","Hold-in power consumption in VA":"26 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C)) 26 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0837c1b2c359635659b16d448f9ba743.pdf","sourceUrl":"https://www.se.com/ie/en/product/LX1D6Z7/tesys-deca-contactor-coil-lx1d6-20-v-ac-50-60-hz-for-40-to-95-a-contactor/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1D6Z7/alternatives.json"},"ai":{"faq":[{"question":"What contactor does this coil fit?","answer":"It is a replacement coil for TeSys Deca contactors rated 40 to 95 A."},{"question":"Does this coil have a built-in suppressor?","answer":"No, it is listed as 'Without built-in suppressor module'."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1D6Z7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1D6Z7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}