{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1FF026","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1FF026","canonicalUrl":"https://aoctrl.com/schneider/LX1FF026","factsUrl":"https://aoctrl.com/api/mcp/products/LX1FF026","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F LX1FF026 contactor coil, 26 V AC 50 Hz, active production.","salesMarkdown":"The LX1FF026 is a replacement coil for TeSys F contactors, wound for 26 V AC at 50 Hz. That 26 V is the control voltage — not the main power — so it pulls in the contactor armature when the control circuit energises it. The coil draws 550 VA inrush at 50 Hz (cos φ 0.3) and holds at 45 VA, which tells you the control transformer needs to be sized for the inrush peak, not the sealed VA. Heat dissipation runs 12 to 16 W at 50 Hz; that's the thermal load the enclosure has to shed if the contactor is cycled hard. The coil has no built-in suppressor module, so you'll need to add a flyback diode or RC snubber across the coil terminals if the control circuit drives inductive loads or a PLC output. Without it, the inductive kick when the coil de-energises can couple noise into nearby signal wiring — check the shield first if you see phantom faults on a sensor line sharing the same panel. ## Voltage tolerance and timing The coil picks up reliably between 85% and 110% of Uc (22.1 V to 28.6 V) and drops out between 35% and 55% (9.1 V to 14.3 V) at 55 °C. That dropout margin is wide enough that a sagging 24 V control bus won't cause nuisance dropouts — the coil stays sealed until the bus dips below about 9 V. Closing time is 23 to 35 ms; opening is 5 to 15 ms, fast enough for most motor-starting and interlocking sequences.","metaTitle":"TeSys LX1FF026 Contactor Coil, 26 V AC 50 Hz, Active","metaDescription":"TeSys F LX1FF026 contactor coil, 26 V AC 50 Hz, active production. 12-16 W heat dissipation, 10 Mcycles mechanical durability, no built-in suppressor.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Coil Voltage":"26 V AC 50 Hz","Operating Time":"23...35 ms closing 5...15 ms opening","Product Status":"Active","Temp Operating Max":"55 °C","Temp Operating Min":"-5 °C","Control Circuit Type":"AC 50 Hz","Mechanical Life Cycles":"10 Mcycles","Main Product Or Component Type":"Contactor coil","Ambient Air Temperature Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e0fbab592be7e783de1e22a8e41b812a.pdf","sourceUrl":"https://www.se.com/vn/en/product/LX1FF026/contactor-coil-tesys-f-lx1ff-26-v-ac-50-hz/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1FF026/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1FF026","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1FF026 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}