{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1FF2206","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1FF2206","canonicalUrl":"https://aoctrl.com/schneider/LX1FF2206","factsUrl":"https://aoctrl.com/api/mcp/products/LX1FF2206","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F, contactor coil LX1FF2206, 220 V AC 60 Hz, 660 VA inrush, 55 VA hold, without built-in suppressor module.","salesMarkdown":"The LX1FF2206 is a replacement contactor coil from the Schneider Electric TeSys F range, designed for 220 V AC 60 Hz control circuits. It is the coil that energizes the main power contacts in a TeSys F contactor — no built-in suppressor module, so you add the RC snubber or varistor externally per the panel design. The closing time spans 23 to 35 ms, opening 5 to 15 ms, which is typical for this frame size and means the contactor responds fast enough for motor starting but not so fast it causes nuisance chatter on a sagging line. Inrush power hits 660 VA at 60 Hz with a 0.3 power factor — that is the surge the control transformer or PLC output must deliver for the 20 ms or so the coil takes to seat. Once sealed, hold-in drops to 55 VA at the same power factor, so the steady-state load on the 24 VDC supply (if you are using an interposing relay) is modest. The coil draws about 2.9 A inrush and 0.25 A hold at 220 V — check your control transformer sizing against the inrush figure if you are driving multiple coils from one source. Drop-out voltage is 0.35 to 0.55 Uc (77 to 121 V at 220 V nominal), operational range is 0.85 to 1.1 Uc (187 to 242 V). That means the coil drops out cleanly on a brownout but stays pulled in through normal line variation. Heat dissipation runs 12 to 16 W at 60 Hz — enough that you should not pack it tight against heat-sensitive components in the enclosure without some air movement. That is a high-duty rating — suitable for frequent cycling applications like conveyor indexing or press control, not just occasional motor starting. ## Integration notes for panel builders The coil mounts directly onto the TeSys F contactor frame — no adapter plate needed. Because there is no built-in suppressor, you must add a flyback diode or RC snubber across the coil terminals if the control circuit uses a PLC or solid-state output; the 2.5 H inductance of the closed circuit will generate a significant voltage spike on de-energization without suppression. Average DC resistance is 18.9 Ω at 20 °C, useful for verifying the coil is not shorted during incoming inspection.","metaTitle":"TeSys LX1FF2206 contactor coil, 220 V AC 60 Hz, obsolete","metaDescription":"TeSys F contactor coil LX1FF2206, 220 V AC 60 Hz, 660 VA inrush, 55 VA hold. Obsolete — sourced to order against RFQ. No direct replacement listed.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","Category":"22341-CONTACTOR,D,K,&F ACCESS","Operating time":"23...35 ms closing 5...15 ms opening","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Heat dissipation":"12...16 W 60 Hz","Device short name":"LX1FF","Average resistance":"18.9 Ohm 68 °F (20 °C)","Inrush power in VA":"660 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))","Control circuit type":"AC 60 Hz","Mechanical durability":"10 Mcycles","Nbr. of units in pkg.":"1","Maximum operating rate":"2400 cyc/h 131 °F (55 °C)","Product or Component Type":"Contactor coil","Inductance of closed circuit":"2.5 H","[Uc] control circuit voltage":"220 V AC 60 Hz","Control circuit voltage limits":"Drop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C)) Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C))","Hold-in power consumption in VA":"55 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fce403fee54fa4c1d06e1d5775709861.pdf","sourceUrl":"https://www.se.com/us/en/product/LX1FF2206/tesys-f-contactor-coil-lx1ff-220-v-ac-60-hz/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1FF2206/alternatives.json"},"ai":{"faq":[{"question":"What is the closest pin-compatible alternative to LX1FF2206 in the TeSys F range?","answer":"No official successor or direct replacement order code is documented in the lifecycle record for this part. Any substitution would require a deviation approval against the customer's approved manufacturer list."},{"question":"What is the control circuit voltage for LX1FF2206?","answer":"220 V AC at 60 Hz. The coil is designed for 60 Hz control circuits only — not 50 Hz or DC. Operating range is 187 to 242 V; dropout occurs between 77 and 121 V."},{"question":"Does this coil include a built-in suppressor module?","answer":"No. The coil technology is listed as without built-in suppressor module. An external RC snubber or flyback diode must be added across the coil terminals when driven by a solid-state output or PLC."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1FF2206","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1FF2206 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}