{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1FG026","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1FG026","canonicalUrl":"https://aoctrl.com/schneider/LX1FG026","factsUrl":"https://aoctrl.com/api/mcp/products/LX1FG026","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F contactor coil, LX1FG026, 26 V AC 50 Hz, 805 VA inrush, 55 VA hold-in, obsolete.","salesMarkdown":"The LX1FG026 is a TeSys F contactor coil from Schneider Electric, rated for 26 V AC at 50 Hz control circuits. It pulls 805 VA inrush at cos φ 0.3 and settles to 55 VA hold-in — numbers you need to size the control transformer feeding it. No built-in suppressor module means you add an RC snubber or varistor across the coil if the PLC output or relay driving it expects one. Drop-out threshold is 0.35 to 0.55 Uc; operational range is 0.85 to 1.1 Uc at 50/60 Hz and 131 °F (55 °C). Heat dissipation is 18 to 24 W at 50 Hz. This part is marked obsolete by Schneider Electric. This coil mounts into TeSys F contactor frames — the full-size F-line power stack. It is an AC 50 Hz coil only; do not apply it on 60 Hz control circuits without checking the drop-out and operational limits, which are specified at 50/60 Hz. The 20 to 35 ms closing time and 7 to 15 ms opening time are standard for this frame class and coordinate with typical PLC scan cycles or relay logic.","metaTitle":"Schneider LX1FG026 TeSys F Contactor Coil, 26 V AC 50 Hz, Ob","metaDescription":"Obsolete LX1FG026 TeSys F contactor coil, 26 V AC 50 Hz, 805 VA inrush, 55 VA hold-in. Sourced to order against RFQ via qualified surplus channels.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","Category":"22341-CONTACTOR,D,K,&F ACCESS","Operating time":"20...35 ms closing 7...15 ms opening","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Heat dissipation":"18...24 W 50 Hz","Device short name":"LX1FG","Average resistance":"0.17 Ohm 68 °F (20 °C)","Inrush power in VA":"805 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))","Control circuit type":"AC 50 Hz","Mechanical durability":"10 Mcycles","Nbr. of units in pkg.":"1","Maximum operating rate":"2400 cyc/h 131 °F (55 °C)","Product or Component Type":"Contactor coil","Inductance of closed circuit":"0.03 H","[Uc] control circuit voltage":"26 V AC 50 Hz","Control circuit voltage limits":"Drop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C)) Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C))","Hold-in power consumption in VA":"55 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/43999d427ba11e50dd3e533db770a9db.pdf","sourceUrl":"https://www.se.com/sg/en/product/LX1FG026/contactor-coil-tesys-f-lx1fg-24-v-ac-50-hz/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1FG026/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to LX1FG026?","answer":"No official successor is listed in the lifecycle data. A functionally equivalent coil would need to match the 26 V AC 50 Hz control voltage, the TeSys F mounting footprint, and the inrush/hold-in power characteristics. Because the LX1FG series was discontinued without a drop-in replacement, verify coil resistance and inductance against your existing unit when sourcing from surplus stock."},{"question":"What are the power consumption ratings?","answer":"Inrush power is 805 VA at 50 Hz with cos φ 0.3, and hold-in power is 55 VA at the same conditions. Heat dissipation runs 18 to 24 W at 50 Hz."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1FG026","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1FG026 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}