{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1FG032","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1FG032","canonicalUrl":"https://aoctrl.com/schneider/LX1FG032","factsUrl":"https://aoctrl.com/api/mcp/products/LX1FG032","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F contactor coil, LX1FG032, 32 V AC 50 Hz, 805 VA inrush, 55 VA hold, obsolete.","salesMarkdown":"The LX1FG032 is a replacement coil for the TeSys F contactor range, wound for 32 V AC at 50 Hz. It pulls 805 VA inrush at 50 Hz (cos φ 0.3) and settles to 55 VA hold-in — the heat dissipation runs 18 to 24 W at 50 Hz, so the enclosure needs some breathing if the contactor cycles hard. Closing time is 20 to 35 ms; opening is 7 to 15 ms. Drop-out voltage sits between 0.35 and 0.55 Uc at 55 °C; pick-up is 0.85 to 1.1 Uc. No built-in suppressor module, so you'll add a varistor or RC snubber across the coil if the PLC output or relay driving it needs protection. Ambient temperature range for operation is -5 to 55 °C. The coil's DC resistance is 0.3 ohm at 20 °C, and closed-circuit inductance is 0.05 H. These numbers matter if you're calculating thermal rise in a densely packed panel or sizing the control transformer.","metaTitle":"Schneider LX1FG032 TeSys F Contactor Coil, 32 V AC 50 Hz","metaDescription":"Obsolete TeSys F contactor coil, 32 V AC 50 Hz, 805 VA inrush, 55 VA hold. Sourced to order against RFQ. No direct replacement listed.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","Category":"22341-CONTACTOR,D,K,&F ACCESS","Operating time":"20...35 ms closing 7...15 ms opening","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Heat dissipation":"18...24 W 50 Hz","Device short name":"LX1FG","Average resistance":"0.3 Ohm 68 °F (20 °C)","Inrush power in VA":"805 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))","Control circuit type":"AC 50 Hz","Mechanical durability":"10 Mcycles","Nbr. of units in pkg.":"1","Maximum operating rate":"2400 cyc/h 131 °F (55 °C)","Product or Component Type":"Contactor coil","Inductance of closed circuit":"0.05 H","[Uc] control circuit voltage":"32 V AC 50 Hz","Control circuit voltage limits":"Drop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C)) Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C))","Hold-in power consumption in VA":"55 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4627d661f6f231fe4a16e0a171b52798.pdf","sourceUrl":"https://www.se.com/sg/en/product/LX1FG032/contactor-coil-tesys-f-lx1fg-32-v-ac-50-hz/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1FG032/alternatives.json"},"ai":{"faq":[{"question":"What are the key electrical ratings for this coil?","answer":"Control voltage is 32 V AC 50 Hz. Inrush power is 805 VA at 50 Hz (cos φ 0.3); hold-in power is 55 VA at 50 Hz (cos φ 0.3). Heat dissipation is 18 to 24 W at 50 Hz."},{"question":"Does the coil include a built-in suppressor?","answer":"No — it is specified without a built-in suppressor module. An external varistor or RC snubber should be added for inductive kickback protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1FG032","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1FG032 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}