{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1FG084","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1FG084","canonicalUrl":"https://aoctrl.com/schneider/LX1FG084","factsUrl":"https://aoctrl.com/api/mcp/products/LX1FG084","rawCanonicalId":null},"summary":{"shortDescription":"TeSys F, contactor coil, LX1FG084, 84 V AC 50 Hz, obsolete.","salesMarkdown":"The LX1FG084 is a replacement contactor coil from the TeSys F range, designed for 84 V AC 50 Hz control circuits. It is the energizing component for a TeSys F contactor, drawing inrush power of 805 VA at 50 Hz and holding at 55 VA (cos φ 0.3, at 68 °F). The coil operates with a closing time of 20...35 ms and an opening time of 7...15 ms. Control circuit voltage limits are drop-out at 0.35...0.55 Uc and operational at 0.85...1.1 Uc at 131 °F (55 °C). ## Key Ratings and Their Meaning for Fit The coil dissipates 18...24 W at 50 Hz. For a panel-builder or MRO planner: this heat load must be accounted for in the enclosure thermal budget, especially if the contactor cycles near its maximum operating rate of 2400 cycles per hour at 131 °F (55 °C). The mechanical durability of 10 Mcycles means the coil itself is not the life-limiting component in most cyclic applications. The coil has no built-in suppressor module. For a controls integrator: this means an external RC snubber or varistor must be added across the coil terminals if the control circuit includes a PLC output or solid-state relay, per standard wiring practice for inductive loads. The average resistance is 2.22 Ω at 68 °F (20 °C), and the inductance of the closed circuit is 0.37 H.","metaTitle":"TeSys LX1FG084 Contactor Coil, 84 V AC 50 Hz, Obsolete","metaDescription":"LX1FG084 is an obsolete TeSys F contactor coil, 84 V AC 50 Hz control circuit. Sourced to order against RFQ. 18-24 W heat dissipation at 50 Hz.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","Category":"22341-CONTACTOR,D,K,&F ACCESS","Operating time":"20...35 ms closing 7...15 ms opening","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Heat dissipation":"18...24 W 50 Hz","Device short name":"LX1FG","Average resistance":"2.22 Ohm 68 °F (20 °C)","Inrush power in VA":"805 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C)) 970 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))","Control circuit type":"AC 50 Hz","Mechanical durability":"10 Mcycles","Nbr. of units in pkg.":"1","Maximum operating rate":"2400 cyc/h 131 °F (55 °C)","Product or Component Type":"Contactor coil","Inductance of closed circuit":"0.37 H","[Uc] control circuit voltage":"84 V AC 50 Hz 100 V AC 60 Hz","Control circuit voltage limits":"Drop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C)) Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C))","Hold-in power consumption in VA":"55 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C)) 66 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/54f9dde5c22dcf4d1b9da2bb8a53684c.pdf","sourceUrl":"https://www.se.com/sg/en/product/LX1FG084/contactor-coil-tesys-f-lx1fg-84-v-ac-50-hz/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1FG084/alternatives.json"},"ai":{"faq":[{"question":"What is LX1FG084's listed range (TeSys) on this component line?","answer":"The LX1FG084 belongs to the TeSys range, specifically the TeSys F series of contactor components."},{"question":"What is LX1FG084's listed category (22341-CONTACTOR,D,K,&F ACCESS) on this component line?","answer":"The category is 22341-CONTACTOR,D,K,&F ACCESS, which classifies it as an accessory for contactors in the D, K, and F frame sizes."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1FG084","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1FG084 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}