{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1FG154","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1FG154","canonicalUrl":"https://aoctrl.com/schneider/LX1FG154","factsUrl":"https://aoctrl.com/api/mcp/products/LX1FG154","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F range, LX1FG154 contactor coil, 154 V AC 50 Hz, 805 VA inrush, 55 VA hold-in, 18...24 W heat dissipation.","salesMarkdown":"The LX1FG154 is a replacement contactor coil from the TeSys F range, wound for 154 V AC 50 Hz control circuits. It's the energizing element for a TeSys F frame contactor — when the coil pulls in, the main poles close and the auxiliary contacts switch. Rated for 805 VA inrush at 50 Hz (cos φ 0.3) dropping to 55 VA hold-in, so the coil sees a heavy initial surge that the control transformer must support without voltage sag. Heat dissipation runs 18...24 W at 50 Hz, which matters for enclosure thermal rise when multiple coils are energized in the same panel. Closing time is 20...35 ms, opening 7...15 ms — fast enough for motor starting duty but not for high-speed synchronous switching. Mechanical durability is 10 Mcycles, so the coil itself is rarely the wear item in a standard panel (the main contacts and arc chambers go first). Maximum operating rate is 2400 cycles/hour at 55 °C; above that, the thermal rise in the coil windings accelerates insulation aging. Control voltage limits are drop-out at 0.35...0.55 Uc and operational pick-up at 0.85...1.1 Uc at 55 °C — meaning the coil drops out cleanly below about 54 V AC and reliably picks up above 131 V AC. If your control supply dips during a downstream fault, this coil may chatter or drop. ## Coil construction note This coil ships without a built-in suppressor module. The inductance of the closed circuit is 1.27 H, and average DC resistance is 8.19 Ω at 20 °C. Without an external RC snubber or varistor across the coil terminals, the inductive kick when de-energizing can couple noise into adjacent control wiring — standard practice is to fit a suppressor (e.g., TeSys LA4 or a generic RC unit) across the coil if the PLC output or relay driving it doesn't have one built in.","metaTitle":"TeSys LX1FG154 Contactor Coil, 154 V AC 50 Hz, Obsolete","metaDescription":"TeSys LX1FG154 contactor coil, 154 V AC 50 Hz, 805 VA inrush, 55 VA hold-in. Obsolete — sourced to order against RFQ. Part of the TeSys F range.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Coil Voltage":"154 V AC 50 Hz","Operating Time":"20...35 ms closing 7...15 ms opening","Product Status":"Active","Temp Operating Max":"55 °C","Temp Operating Min":"-5 °C","Control Circuit Type":"AC 50 Hz","Mechanical Life Cycles":"10 Mcycles","Main Product Or Component Type":"Contactor coil","Ambient Air Temperature Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/82461c8e0198d2a776cd6d560a4749b6.pdf","sourceUrl":"https://www.se.com/th/en/product/LX1FG154/contactor-coil-tesys-f-lx1fg-154-v-ac-50-hz/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1FG154/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1FG154","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1FG154 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}