{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1FG264","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1FG264","canonicalUrl":"https://aoctrl.com/schneider/LX1FG264","factsUrl":"https://aoctrl.com/api/mcp/products/LX1FG264","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F contactor coil, LX1FG264, 264 V AC 50 Hz, 805 VA inrush, 55 VA hold-in, 18-24 W heat dissipation.","salesMarkdown":"The LX1FG264 is a replacement coil for the TeSys F contactor range, wound for 264 V AC 50 Hz control circuits. It pulls 805 VA inrush at 50 Hz (cos φ 0.3) and settles to 55 VA hold-in — the inrush figure is what the control transformer and wiring need to handle, not just the sealed draw. Heat dissipation runs 18 to 24 W at 50 Hz, so panel thermal rise is a real consideration if multiple coils are ganged on the same enclosure. ## Switching performance and duty cycle Closing time is 20 to 35 ms, opening 7 to 15 ms. That's fast enough for most motor-start and lighting contactor applications, but if you're sequencing contactors in a reversing starter, account for the 20 ms minimum close time in your interlock timing. The coil is rated for 2400 cycles per hour at 131 °F (55 °C) ambient, and mechanical durability is 10 million cycles — the coil itself won't be the wear-out item in normal use. ## Coil voltage tolerance and suppressor note Pickup voltage range is 0.85 to 1.1 Uc at 50/60 Hz and 131 °F (55 °C); dropout is 0.35 to 0.55 Uc. That means the coil will pull in reliably down to about 224 V AC and drop out below roughly 145 V AC — useful to know if your control supply sags under heavy load. The coil ships without a built-in suppressor module, so you'll need to add an external RC snubber or varistor across the coil if you're switching it with a PLC output or solid-state relay. Coil resistance is 24.52 Ω at 68 °F (20 °C); inductance of the closed circuit is 3.7 H.","metaTitle":"TeSys LX1FG264 Contactor Coil, 264 V AC 50 Hz","metaDescription":"TeSys F contactor coil LX1FG264, 264 V AC 50 Hz. Active production. Inrush 805 VA, hold 55 VA. 18-24 W heat dissipation. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","title":"LX1FG264","Category":"22341-CONTACTOR,D,K,&F ACCESS","description":"contactor coil - TeSys F - LX1FG - 264 V AC - 50 Hz","Operating time":"20...35 ms closing 7...15 ms opening","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Heat dissipation":"18...24 W 50 Hz","Device short name":"LX1FG","Average resistance":"24.52 Ohm 68 °F (20 °C)","Inrush power in VA":"805 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))","Control circuit type":"AC 50 Hz","Mechanical durability":"10 Mcycles","Nbr. of units in pkg.":"1","Maximum operating rate":"2400 cyc/h 131 °F (55 °C)","Product or Component Type":"Contactor coil","Inductance of closed circuit":"3.7 H","[Uc] control circuit voltage":"264 V AC 50 Hz","Control circuit voltage limits":"Drop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C)) Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C))","Hold-in power consumption in VA":"55 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d2c374fa759a2bf2c22fa956b47ba4af.pdf","sourceUrl":"https://www.se.com/th/en/product/LX1FG264/contactor-coil-tesys-f-lx1fg-264-v-ac-50-hz/"},"ai":{"faq":[{"question":"What is the closest alternative to the LX1FG264?","answer":"There is no pin-compatible drop-in alternative outside the TeSys F platform. The LX1FG family includes other coil voltages for the same contactor frame, but the 264 V AC 50 Hz winding is specific to this order code."},{"question":"What control circuit voltage does the LX1FG264 require?","answer":"The coil is rated for 264 V AC at 50 Hz. Pickup range is 0.85 to 1.1 Uc (approx. 224 to 290 V AC), dropout is 0.35 to 0.55 Uc (approx. 92 to 145 V AC)."},{"question":"Does the LX1FG264 include a built-in coil suppression module?","answer":"No, the coil ships without a built-in suppressor module. An external RC snubber or varistor must be added when switching with a PLC output or solid-state relay."},{"question":"What is the heat dissipation of the LX1FG264?","answer":"Heat dissipation is 18 to 24 W at 50 Hz. This should be factored into panel thermal calculations, especially when multiple coils are installed in the same enclosure."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1FG264","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1FG264 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}