{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1FH0202","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1FH0202","canonicalUrl":"https://aoctrl.com/schneider/LX1FH0202","factsUrl":"https://aoctrl.com/api/mcp/products/LX1FH0202","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F contactor coil, LX1FH0202, 20 V AC 40-400 Hz, 8 W heat dissipation, 10 Mcycles mechanical durability.","salesMarkdown":"The LX1FH0202 is a TeSys F contactor coil — the replaceable solenoid that pulls in the main contactor armature. It's a 20 V AC coil rated for 40-400 Hz supply, meaning it works on standard 50/60 Hz control transformers as well as higher-frequency circuits up to 400 Hz (common in aerospace or genset-derived supplies). Opening time runs 100-170 ms, closing 40-65 ms. That's a deliberate slow-open characteristic — helps manage arc extinction on the main contacts. The coil draws 650 VA inrush (cos φ 0.9) and settles to 10 VA holding (cos φ 0.3). Heat dissipation is 8 W across the frequency range. No built-in suppressor module, so you'll need an external RC snubber or varistor across the coil if driving it from a PLC output or solid-state relay. Coil resistance is 0.8 Ω inrush, 20 Ω holding at 20 °C. That's a solid baseline for general-purpose switching; if you're cycling faster or at higher ambient, the thermal derating curve applies (not shown here, but standard for the TeSys F family). ## What to watch when specifying Drop-out threshold is 0.35-0.55 Uc (7-11 V AC) at 55 °C; operational pickup is 0.85-1.1 Uc (17-22 V AC). If your control transformer sags under inrush from other loads, ensure the voltage stays above 17 V during the pickup transient or the coil may chatter. That's typical for panel-mount contactor coils — fine inside a ventilated enclosure, but not for direct outdoor exposure or hot-aisle environments without derating.","metaTitle":"TeSys LX1FH0202 contactor coil, 20 V AC 40-400 Hz","metaDescription":"TeSys F contactor coil LX1FH0202, 20 V AC 40-400 Hz, 8 W heat dissipation, 10 Mcycles mechanical durability. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Coil Voltage":"20 V AC 40...400 Hz","Operating Time":"100...170 ms opening 40...65 ms closing","Product Status":"Active","Temp Operating Max":"55 °C","Temp Operating Min":"-5 °C","Control Circuit Type":"AC 40...400 Hz","Mechanical Life Cycles":"10 Mcycles","Main Product Or Component Type":"Contactor coil","Ambient Air Temperature Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/07f8a1d02ebb14c9f83f70bcdd4a8f0a.pdf","sourceUrl":"https://www.se.com/sg/en/product/LX1FH0202/tesys-f-contactor-coil-lx1fh-20-v-ac-40-400-hz/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1FH0202/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1FH0202","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1FH0202 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}