{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1FH0302","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1FH0302","canonicalUrl":"https://aoctrl.com/schneider/LX1FH0302","factsUrl":"https://aoctrl.com/api/mcp/products/LX1FH0302","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys LX1FH0302 contactor coil, 30 V AC 40-400 Hz, 8 W dissipation, 100-170 ms opening time.","salesMarkdown":"It operates on a 30 V AC control circuit at 40-400 Hz, drawing 8 W of heat dissipation at steady state. Opening time spans 100-170 ms, closing time 40-65 ms, which sets the mechanical response window for the contactor it drives. The coil lacks a built-in suppressor module, so an external RC snubber or varistor is needed across the coil terminals if driving inductive loads or if the PLC output card requires suppression. ## Control voltage limits and thermal derating The coil holds in at 85-110% of rated Uc (25.5-33 V AC) and drops out between 35-55% of Uc (10.5-16.5 V AC) at 55 °C ambient. This dropout margin is generous — the contactor stays sealed through brownout conditions down to roughly 17 V AC, which matters for installations on long cable runs or shared control transformers. Maximum operating rate is 2400 cycles per hour at 55 °C, so continuous high-speed cycling (e.g., resistance welding or fast indexing) stays within the thermal limit. The 8 W dissipation figure is at rated voltage and frequency; panel builders should account for this when sizing enclosure ventilation, especially in sealed cabinets. The TeSys range is widely stocked across the distribution network, so lead times are typically short for this active, non-obsolete part.","metaTitle":"Schneider Electric LX1FH0302 TeSys Contactor Coil, 30 V AC","metaDescription":"Active TeSys LX1FH0302 contactor coil, 30 V AC 40-400 Hz, 8 W dissipation, 100-170 ms opening time. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","title":"LX1FH0302","Category":"22341-CONTACTOR,D,K,&F ACCESS","description":"contactor coil - LX1F - 30 V AC - 40/400 Hz","Operating time":"100...170 ms opening 40...65 ms closing","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Heat dissipation":"8 W 40...400 Hz","Device short name":"LX1FH","Control circuit type":"AC 40...400 Hz","Nbr. of units in pkg.":"1","Maximum operating rate":"2400 cyc/h 131 °F (55 °C)","Product or Component Type":"Contactor coil","[Uc] control circuit voltage":"30 V AC 40...400 Hz","Control circuit voltage limits":"Drop-out 0.35...0.55 Uc 40...400 Hz 131 °F (55 °C)) Operational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C))","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6d9982b643f841e8bcb94733ed406837.pdf","sourceUrl":"https://www.se.com/sg/en/product/LX1FH0302/contactor-coil-lx1f-30-v-ac-40-400-hz/"},"ai":{"faq":[{"question":"What is the closest alternative to LX1FH0302 in the TeSys family?","answer":"Within the LX1F coil family, the closest peer is the LX1FH0301 (24 V AC) and LX1FH0303 (48 V AC). The only difference is the control voltage — form, fit, and function are identical. If your panel uses 24 V AC control, the LX1FH0301 is a direct drop-in; for 48 V AC, the LX1FH0303. No pinout or mounting change."},{"question":"What compliance documentation is available for LX1FH0302?","answer":"As a TeSys component, it carries CE marking for the Low Voltage Directive and RoHS compliance. UL and CSA listings are standard for the LX1F coil family, though the specific listing for this order code should be confirmed on the product certificate."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1FH0302","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1FH0302 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}