{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1FH3202","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1FH3202","canonicalUrl":"https://aoctrl.com/schneider/LX1FH3202","factsUrl":"https://aoctrl.com/api/mcp/products/LX1FH3202","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys LX1FH3202 contactor coil, 316-340 V AC 40-400 Hz, 8 W heat dissipation, obsolete.","salesMarkdown":"The LX1FH3202 is a replacement coil for Schneider Electric TeSys F-series contactors, designed for a control circuit voltage of 316-340 V AC at 40-400 Hz. It dissipates 8 W of heat and has an opening time of 100-170 ms and a closing time of 40-65 ms, with a maximum operating rate of 2400 cycles per hour at 55 °C. The coil lacks a built-in suppressor module, so external suppression (e.g., an RC snubber or varistor) must be added across the coil terminals to protect control electronics from switching transients. Schneider Electric has marked the LX1FH3202 as obsolete. The 316-340 V AC control voltage is non-standard for many panels (common are 230 V or 400-480 V). Verify that your control transformer or supply delivers within this band; the coil operates between 0.85 and 1.1 Uc (roughly 269-374 V) and drops out at 0.35-0.55 Uc (111-187 V). The 8 W heat dissipation at 40-400 Hz means the coil generates measurable heat inside the enclosure. If mounted in a sealed panel with other heat sources, check the ambient temperature stays within -5 to 55 °C to avoid thermal derating of the coil or adjacent components.","metaTitle":"Schneider Electric LX1FH3202 TeSys Contactor Coil, 316-340V","metaDescription":"LX1FH3202 is an obsolete TeSys contactor coil, 316-340V AC 40-400Hz, 8W dissipation. Sourced to order against RFQ. No direct replacement listed.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","Category":"22341-CONTACTOR,D,K,&F ACCESS","Operating time":"100...170 ms opening 40...65 ms closing","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Heat dissipation":"8 W 40...400 Hz","Device short name":"LX1FH","Control circuit type":"AC 40...400 Hz","Nbr. of units in pkg.":"1","Maximum operating rate":"2400 cyc/h 131 °F (55 °C)","Product or Component Type":"Contactor coil","[Uc] control circuit voltage":"316...340 V AC 40...400 Hz","Control circuit voltage limits":"Drop-out 0.35...0.55 Uc 40...400 Hz 131 °F (55 °C)) Operational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C))","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/39b0cbbb984a2dcbb8497c951b9b762c.pdf","sourceUrl":"https://www.se.com/sg/en/product/LX1FH3202/contactor-coil-lx1f-316340v-ac-40-400hz/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1FH3202/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to LX1FH3202?","answer":"No official successor or pin-compatible alternative is listed in the lifecycle record. For a drop-in replacement, you would need to cross-reference the contactor frame size and coil voltage with a current TeSys F-series coil catalog."},{"question":"What is the operating voltage range of this coil?","answer":"The control circuit voltage is 316-340 V AC at 40-400 Hz. The coil operates between 0.85 and 1.1 Uc and drops out between 0.35 and 0.55 Uc."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1FH3202","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1FH3202 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}