{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1FH7002","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1FH7002","canonicalUrl":"https://aoctrl.com/schneider/LX1FH7002","factsUrl":"https://aoctrl.com/api/mcp/products/LX1FH7002","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F contactor coil, LX1FH7002, 700 V AC 40...400 Hz, 650 VA inrush, 10 VA hold, obsolete.","salesMarkdown":"The LX1FH7002 is a TeSys F contactor coil from Schneider Electric, designed to operate the main poles of a TeSys F contactor at 700 V AC, 40...400 Hz. It is a replacement coil, not a complete contactor — you pair it with the matching contactor frame. This coil draws 650 VA inrush at 20 °C (cos φ 0.9) and settles to 10 VA holding power (cos φ 0.3). The 8 W heat dissipation at rated frequency means the panel builder should allow airflow around the contactor — especially if multiple units are ganged. Operating time is 100...170 ms to open, 40...65 ms to close — typical for a large-frame AC coil. The mechanical durability of 10 Mcycles is generous for a coil this size, but the maximum operating rate of 2400 cycles/hour at 55 °C sets a practical limit for high-speed applications like motor reversing or capacitor switching. Schneider has marked the LX1FH7002 as obsolete. ## Electrical Fit — What the Ratings Mean The control circuit voltage is 700 V AC, 40...400 Hz — this is a high-voltage coil, not a standard 24 V or 230 V unit. The operational voltage limits are 0.85...1.1 Uc (595...770 V AC) at 55 °C, and drop-out occurs at 0.35...0.55 Uc (245...385 V AC). If your control supply sags below 595 V, the contactor may not pull in reliably. Coil resistance is 0.8 Ω inrush and 20 Ω holding at 20 °C. The inrush current can be calculated from the 650 VA figure — roughly 0.93 A at 700 V — but the holding current drops to about 14 mA. The coil has no built-in suppressor module, so you must add an external RC snubber or varistor if driving it from a PLC output or solid-state relay. The coil is rated for AC control circuits only (40...400 Hz) — do not apply DC voltage.","metaTitle":"TeSys LX1FH7002 Contactor Coil, 700 VAC 40-400 Hz, Obsolete","metaDescription":"TeSys F LX1FH7002 contactor coil, 700 VAC 40-400 Hz, 650 VA inrush, 10 VA hold. Obsolete — sourced to order against RFQ. No direct successor listed.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Coil Voltage":"700 V AC 40...400 Hz","Operating Time":"100...170 ms opening 40...65 ms closing","Product Status":"Active","Temp Operating Max":"55 °C","Temp Operating Min":"-5 °C","Control Circuit Type":"AC at 40...400 Hz","Mechanical Life Cycles":"10 Mcycles","Main Product Or Component Type":"Contactor coil","Ambient Air Temperature Operation":"-5...55 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b561f9ba94b7a156618bead46a3e7ace.pdf","sourceUrl":"https://www.se.com/ie/en/product/LX1FH7002/tesys-f-contactor-coil-lx1fh-700-v-ac-40-400-hz/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1FH7002/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1FH7002","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1FH7002 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}