{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1FH7502","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1FH7502","canonicalUrl":"https://aoctrl.com/schneider/LX1FH7502","factsUrl":"https://aoctrl.com/api/mcp/products/LX1FH7502","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys LX1F series, LX1FH7502 contactor coil, 780..800 V AC 40/400 Hz, 8 W dissipation, 100-170 ms opening time.","salesMarkdown":"The LX1FH7502 is a TeSys LX1F-series contactor coil rated for 780...800 V AC control circuits at 40 to 400 Hz. It pulls 8 W of heat dissipation during continuous operation, so panel ventilation or spacing from heat-sensitive components matters in a crowded enclosure. Opening time runs 100 to 170 ms; closing is faster at 40 to 65 ms. That spread matters for sequencing — if you're coordinating interlocking or safety circuits, the slower opening side sets the window you need to guarantee separation. ## Control voltage limits and operating conditions The coil holds in from 85% to 110% of rated Uc (operational range) and drops out between 35% and 55% Uc at 55 °C. That dropout threshold is low enough that a sagging line won't cause nuisance dropouts, but verify your supply's brownout behavior against the 0.35 Uc floor — roughly 273 V AC on a 780 V nominal tap. Rated for ambient temperatures from -5 to 55 °C. Maximum cycling rate is 2400 operations per hour at 55 °C — enough for most motor-starting duty, but if you're running a high-speed pick-and-place or cam-driven load, check the thermal accumulation against the 8 W dissipation figure.","metaTitle":"Schneider Electric LX1FH7502 TeSys Contactor Coil, 780-800 V","metaDescription":"Active TeSys contactor coil LX1FH7502, 780-800 V AC 40-400 Hz, 8 W dissipation, 100-170 ms opening time. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Coil Voltage":"780...800 V AC 40...400 Hz","Operating Time":"100...170 ms opening 40...65 ms closing","Product Status":"Active","Temp Operating Max":"55 °C","Temp Operating Min":"-5 °C","Control Circuit Type":"AC 40...400 Hz","Main Product Or Component Type":"Contactor coil","Ambient Air Temperature Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/efe77be745cfec0d5373107a93fcbc57.pdf","sourceUrl":"https://www.se.com/th/en/product/LX1FH7502/contactor-coil-lx1f-780-800-v-ac-40-400-hz/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1FH7502/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1FH7502","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1FH7502 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}