{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1FK1106","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1FK1106","canonicalUrl":"https://aoctrl.com/schneider/LX1FK1106","factsUrl":"https://aoctrl.com/api/mcp/products/LX1FK1106","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys LX1F series, LX1FK1106 contactor coil, 100-110 V AC 50/60 Hz, 166 Ohm holding resistance, without built-in suppressor module.","salesMarkdown":"The LX1FK1106 is a replacement contactor coil from the Schneider TeSys LX1F range, designed for 100-110 V AC control circuits at 50/60 Hz. It is the energizing component that pulls in the contactor armature — without it, the main power contacts don't close. The coil draws 7.53 Ohm inrush at 20 °C, settling to 166 Ohm holding once the armature seats. Opening time runs 100-170 ms; closing time is faster at 40-75 ms. No built-in suppressor module is included, so you will need to add an external RC snubber or varistor across the coil terminals if driving from a PLC output or electronic controller. The control voltage limits are worth noting: the coil operates reliably between 0.85 and 1.1 Uc (85-110 V AC at 50/60 Hz, 55 °C ambient). Dropout occurs between 0.3 and 0.5 Uc (30-50 V AC) — meaning if your control supply sags below that threshold, the contactor drops out and the load disconnects. The average holding resistance of 166 Ohm at 20 °C gives a steady-state current draw of roughly 0.6 A at 100 V AC — factor that into your control transformer sizing if multiple coils are energized simultaneously. ## Integration note Mounts directly onto the TeSys LX1F contactor frame — the coil clips onto the magnet assembly. No built-in suppressor; plan for an external suppression network if switched by a solid-state output.","metaTitle":"Schneider TeSys LX1FK1106 Contactor Coil, 100-110 V AC","metaDescription":"TeSys LX1FK1106 replacement contactor coil. 100-110 V AC 50/60 Hz, 166 Ohm holding resistance. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","title":"LX1FK1106","description":"contactor coil - LX1F - 100..110 V - 50/60 Hz","Operating time":"100...170 ms opening 40...75 ms closing","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Device short name":"LX1FK","Average resistance":"166 Ohm holding at 20 °C 7.53 Ohm inrush at 20 °C","Control circuit type":"AC at 50/60 Hz","Mechanical durability":"10 Mcycles","Maximum operating rate":"2400 cyc/h 55 °C","Product or component type":"Contactor coil","[Uc] control circuit voltage":"100 V AC 50 Hz 100...110 V AC 60 Hz","Control circuit voltage limits":"Operational: 0.85...1.1 Uc 50/60 Hz (at 55 °C) Drop-out: 0.3...0.5 Uc 50/60 Hz (at 55 °C)","Ambient air temperature for operation":"-5...55 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/bb69b11bdc296cf00803f742deb6bfa1.pdf","sourceUrl":"https://www.se.com/sg/en/product/LX1FK1106/contactor-coil-lx1f-100-110-v-50-60-hz/"},"ai":{"faq":[{"question":"What is the operating time of the LX1FK1106?","answer":"Opening time is 100 to 170 ms; closing time is 40 to 75 ms. These are the mechanical travel times of the contactor armature when the coil is energized or de-energized at rated voltage."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1FK1106","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1FK1106 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}