{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1FK415","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1FK415","canonicalUrl":"https://aoctrl.com/schneider/LX1FK415","factsUrl":"https://aoctrl.com/api/mcp/products/LX1FK415","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F LX1FK415 contactor coil, 415...440 V AC 40...400 Hz, 1100 VA inrush, 18 VA holding.","salesMarkdown":"## Contactor coil for TeSys F The LX1FK415 is the 415...440 V AC 40...400 Hz coil for the TeSys F contactor range. It draws 1100 VA at inrush and 18 VA holding, dissipating 18 W. Opening time runs 100...170 ms, closing 40...75 ms. This coil ships without a built-in suppressor module. If the application requires surge suppression for the control circuit, an external RC snubber or varistor needs to be added at the coil terminals. The holding coil resistance is 3730 Ω at 20 °C.","metaTitle":"Schneider LX1FK415 TeSys F Coil, 415V AC, 1100VA","metaDescription":"Active-production TeSys F contactor coil for 415-440 VAC 40-400 Hz. 1100 VA inrush, 18 W holding. Sourced to order. RFQ for BOM fill or critical spare.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Range":"TeSys","Category":"US10I1222341","Operating time":"100...170 ms opening 40...75 ms closing","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Heat dissipation":"18 W 40...400 Hz","Device short name":"LX1FK","Average resistance":"143 Ohm inrush 68 °F (20 °C) 3730 Ohm holding 68 °F (20 °C)","Inrush power in VA":"1100 VA 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))","Control circuit type":"AC 40...400 Hz","Mechanical durability":"10 Mcycles","Nbr. of units in pkg.":"1","Maximum operating rate":"2400 cyc/h 131 °F (55 °C)","Product or Component Type":"Contactor coil","Inductance of closed circuit":"18.4 H","[Uc] control circuit voltage":"415 V AC 40...400 Hz","Control circuit voltage limits":"Operational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 40...400 Hz 131 °F (55 °C))","Hold-in power consumption in VA":"18 VA 40...400 Hz cos phi 0.3 (at 68 °F (20 °C))","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$227.33 – $441.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2370324529ec7527708fd184747ddec8.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1FK415/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1FK415","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1FK415 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}